8-52 DC Brake Select
Option:
Function:
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
Select control of the DC brake via the terminals
(digital input).
[0] Digital
input
Activates DC brake via a digital input.
[1] Bus
Activates DC brake via the serial communication
port.
[2] Logic
AND
Activates DC brake via the serial communication
port, and via 1 of the digital inputs.
[3] Logic OR Activates DC brake via the serial communication
port or via 1 of the digital inputs.
8-53 Start Select
Option:
Function:
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
Select control of the frequency converter start
function via the terminals (digital input).
[0]
Digital
input
Activates a start command via a digital input.
[1]
Bus
Activates a start command via the serial
communication port or fieldbus options.
[2]
Logic
AND
Activates a start command via the serial
communication port, and via 1 of the digital
inputs.
[3]
*
Logic
OR
Activates a start command via the serial
communication port or via 1 of the digital inputs.
8-54 Reversing Select
Option:
Function:
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
Select control of the frequency converter
Reverse
function via the terminals (digital input) and/or
via the serial communication port.
[0]
*
Digital
input
Activates a reverse command via a digital input.
[1]
Bus
Activates a reverse command via the serial
communication port.
8-54 Reversing Select
Option:
Function:
[2]
Logic
AND
Activates a reverse command via the serial
communication port, and via 1 of the digital
inputs.
[3]
Logic
OR
Activates a reverse command via the serial
communication port or via 1 of the digital inputs.
8-55 Set-up Select
Option:
Function:
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the serial communication port.
[0]
Digital
input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port.
[2]
Logic
AND
Activates the set-up selection via the serial
communication port, and via 1 of the digital
inputs.
[3]
*
Logic
OR
Activate the set-up selection via the serial
communication port or via 1 of the digital inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter preset
reference selection via the terminals (digital
input) and/or via the serial communication port.
[0]
Digital
input
Activates the preset reference selection via a
digital input.
[1]
Bus
Activates the preset reference selection via the
serial communication port.
[2]
Logic
AND
Activates the preset reference selection via the
serial communication port, and via 1 of the
digital inputs.
[3]
*
Logic OR
Activates the preset reference selection via the
serial communication port or via 1 of the digital
inputs.
8-57 Profidrive OFF2 Select
Select control of the frequency converter OFF2 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
parameter 8-01 Control Site
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1]
Profidrive profile
.
Option:
Function:
[0]
Digital input
Parameters
VLT
®
DriveMotor FCP 106/FCM 106
74
Danfoss A/S © 11/2015 All rights reserved.
MG03N202
4
4