4 Parameters
4.1 Main Menu - Operation and Display -
Group 0
Parameters related to the fundamental functions of the
frequency converter, function of the LCP keys, and configu-
ration of the LCP display.
4.1.1 0-0* Basic Settings
0-01 Language
Option:
Function:
Defines the language to be used in the display.
[0]
*
English
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
[28]
Bras.port
[255] No Text
0-03 Regional Settings
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor runs.
To meet the needs for different default settings
in different parts of the world,
parameter 0-03 Regional Settings
is implemented
in the frequency converter. The selected setting
influences the default setting of the motor
nominal frequency.
[0]
*
Interna-
tional
Sets the default value of
to 50 Hz.
[1]
North
America
Sets the default value of
to 60 Hz.
0-04 Operating State at Power-up
Option:
Function:
Select the operating mode after reconnection of
the frequency converter to mains voltage after
power-down when operating in
Hand (local)
mode
.
[0]
*
Resume
Resumes operation of the frequency converter,
maintaining the same local reference and the
same start/stop condition (applied by [Hand
On]/[Off] on the LCP or local start via a digital
input as before the frequency converter was
powered down.
0-04 Operating State at Power-up
Option:
Function:
[1]
Forced
stop,
ref=old
Uses saved reference [1] to stop the frequency
converter, but at the same time retains the local
speed reference in memory before powering
down. After mains voltage is reconnected, and
after receiving a start command (pressing [Hand
On] key or using the local start command via a
digital input), the frequency converter restarts
and operates at the retained speed reference.
0-06 GridType
Option:
Function:
Select the grid type of the supply
voltage/frequency.
NOTICE
Not all options are supported in
all power sizes.
IT grid is a supply mains, where there
are no connections to ground.
Adjust the position of the RFI switch to
match the grid type (refer to
VLT
®
DriveMotor FCP 106/FCM 106 Operating
Instructions
).
Delta is a supply mains where the
secondary part of the transformer is
delta connected, and 1 phase is
connected to ground.
[10]
380-440V/
50Hz/IT-grid
[11]
380-440V/50Hz/
Delta
[12]
380-440V/50Hz
[20]
440-480V/
50Hz/IT-grid
[21]
440-480V/50Hz/
Delta
[22]
440-480V/50Hz
[110] 380-440V/
60Hz/IT-grid
[111] 380-440V/60Hz/
Delta
[112] 380-440V/60Hz
[120] 440-480V/
60Hz/IT-grid
[121] 440-480V/60Hz/
Delta
[122] 440-480V/60Hz
Parameters