6.3 Mains Supply
Mains supply (L1, L2, L3)
Supply voltage
380–480 V
±
10%
Mains voltage low/mains dropout:
•
During low mains voltage or a mains dropout, the frequency converter continues until the DC-link voltage drops below
the minimum stop level. This level typically corresponds to 15% below the lowest rated supply voltage of the frequency
converter. Power-up and full torque cannot be expected at mains voltage lower than 10% below the lowest rated
supply voltage of the frequency converter.
Supply frequency
50/60 Hz
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
True power factor (
λ
)
≥
0.9 nominal at rated load
Displacement power factor (COS
φ
)
Near unity (>0.98)
Switching on the input supply L1, L2, L3 (power-ups)
Maximum 2 times/min.
Environment according to EN 60664-1 and IEC 61800-5-1
Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than:
•
100000 RMS symmetrical Amperes, 480 V maximum, with fuses used as branch circuit protection.
•
See
and
when using circuit breakers as branch circuit protection.
6.4 Protection and Features
Protection and features
•
Electronic motor thermal protection against overload.
•
Temperature monitoring of the heat sink ensures that the frequency converter trips when the temperature reaches
90
°
C (194
°
F)
±
5
°
C (41
°
F). An overload temperature cannot be reset until the temperature of the heat sink is
below 70
°
C (158
°
F)
±
5
°
C (41
°
F). However, these temperatures may vary for different power sizes, enclosures,
and so on. The frequency converter autoderating function ensures that the heat sink temperature does not reach
90
°
C (194
°
F).
•
The frequency converter motor terminals U, V, and W are protected against ground faults at power-up and start of
the motor.
•
When a motor phase is missing, the frequency converter trips and issues an alarm.
•
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
•
Monitoring of the DC-link voltage ensures that the frequency converter trips when the DC-link voltage is too low
or too high.
•
The frequency converter is protected against ground faults on motor terminals U, V, and W.
•
All control terminals and relay terminals 01–03/04–06 comply with PELV (protective extra low voltage). However,
this compliance does not apply to grounded delta leg above 300 V.
6.5 Ambient Conditions
Environment
Enclosure protection rating
IP66/Type 4X
1)
Enclosure protection rating FCP 106 between lid and heat sink
IP66/Type 4X
Enclosure protection rating FCP 106 between heat sink and adapter plate
IP66/Type 4X
FCP 106 wall mount kit
IP66
Stationary vibration IEC61800-5-1 Ed.2
Cl. 5.2.6.4
Non-stationary vibration (IEC 60721-3-3 Class 3M6)
25.0 g
Relative humidity (IEC 60721-3-3; Class 3K4 (non-condensing))
5–95% during operation
Aggressive environment (IEC 60721-3-3)
Class 3C3
Test method according to IEC 60068-2-43
H2S (10 days)
Ambient temperature
40
°
C (104
°
F) (24-hour average)
Specifications
Design Guide
MG03M202
Danfoss A/S © 06/2016 All rights reserved.
67
6
6