8-43 PCD Read Configuration
Select the parameters to be assigned to PCD's of the telegrams.
The number of available PCDs depends on the telegram type.
PCDs contain the actual data values of the selected parameters.
Option:
Function:
[23]
[1652]
Feedback
[Unit]
[24]
[1660] Digital
Input
18,19,27,33
[25]
[1661]
Terminal 53
Switch Setting
[26]
[1662] Analog
input 53
[27]
[1663]
Terminal 54
Switch Setting
[28]
[1664] Analog
input 54
[29]
[1665] Analog
output 42
[mA]
[30]
[1671] Relay
output
[31]
[1672] Counter
A
[32]
[1673] Counter
B
[33]
[1690] Alarm
Word
[34]
[1692]
Warning Word
[35]
[1694] Ext.
Status Word
[37]
[2860] RPS
Readout
[39]
[1691] Alarm
Word 2
[40]
[1693]
Warning Word
2
[43]
[1617] Speed
[RPM]
[44]
[1666] Digital
Output
3.8.4 8-5* Digital/Bus
Parameters for configuring the control word digital/bus
merging.
8-50 Coasting Select
Select control of the coasting function via the terminals (digital
input) and/or via the bus. This parameter is only active when
is set to
[0] Digital and control word
.
Option:
Function:
[0]
Digital input
Activates coast via a digital input.
[1]
Bus
Activates coast via the serial
communication port.
[2]
Logic AND
Activates coast via the fieldbus/
serial communication port, and via
1 of the digital inputs.
[3]
*
Logic OR
Activates coast via the serial
communication port or via 1 of the
digital inputs.
8-51 Quick Stop Select
Select control of the quick stop function via the terminals (digital
input) and/or via the bus. This parameter is only active when
is set to
[0] Digital and control word
.
Option:
Function:
[0]
Digital input
Activates quick stop via a digital
input.
[1]
Bus
Activates quick stop via the serial
communication port.
[2]
Logic AND
Activates quick stop via the serial
communication port and via 1 of
the digital inputs.
[3]
*
Logic OR
Activates quick stop via the serial
communication port or via 1 of the
digital inputs.
8-52 DC Brake Select
Select control of the DC brake via the terminals (digital
input).This parameter is only active when
is set to
[0] Digital and control word
.
Option:
Function:
[0]
Digital input
Activates DC brake via a digital
input.
[1]
Bus
Activates DC brake via the serial
communication port.
[2]
Logic AND
Activates DC brake via the serial
communication port, AND also via
one of the digital inputs.
[3]
*
Logic OR
Activates DC brake via the serial
communication port OR via one of
the digital inputs.
Parameters
Programming Guide
MG18P202
Danfoss A/S © 06/2019 All rights reserved.
43