3.1.5 SDO Communication
All CANopen objects and frequency converter parameters
can be accessed via SDOs (service data objects).
For a description of supported SDO abort codes, refer to
COB-ID
Transmit SDO
1409 (581h)–1535 (5FFh)
580h + Node ID
Receive SDO
1537 (601h)–1663 (67Fh)
600h + Node ID
Table 3.5 COB-ID’s for SDO Communication
COB-ID CS
OD-Index Sub-ind.
Data
600+ID See following text 01
20
00
00 00 00 00
Table 3.6 Structure of a SDO-message (Request)
The CS-field contains the command and response
specifiers. See
and
.
Command
CS
Write request 4 bytes
23h
Write request 2 bytes
2Bh
Write request 1 byte
2Fh
Read request (any)
40h
Table 3.7 Command
Response
CS
Write response (any)
60h
Read response 4 bytes
43h
Read response 2 bytes
4Bh
Read response 1 byte
4Fh
Error response
80h
Table 3.8 Response
Saving OD entries
In standard configuration, all para OD entries are
stored in volatile (RAM) memory only. To store current
network configuration in non-volatile memory, use OD
index 1010h.
To save parameters, write the value 65766173 (save) to the
appropriated sub-index in OD: 1010h.
OD index Subindex Description
1010h
0
Number of entries
1
Save all para OD entries
2
Save all communication para OD
entries
3
Reserved
4
Save edit set-up (Danfoss specific)
Table 3.9 Saving OD Entries
Restoring OD entries
To restore factory defaults, use OD index 1011h.
To restore default parameters the value “
64616F6C
” (load)
must be written to the appropriated sub-index in OD:
1011h
OD index Subindex Description
1011h
0
Number of entries
1
Restore all para OD entries*
2
Restore all communication para
OD entries and restart
Table 3.10 Restoring OD Entries
* requires power cycle
NOTICE
Frequency converter displays Alarm 80 “Drive initialised”
after restores.
3.2 Configure the Master
3.2.1 EDS File
A large part area of the system configuration is the setting
of application-related parameters. EDS (electronic data
sheet) files simplify the setting up of most of the CANopen
configurable parameters. The EDS file contains all
supported communication-specific objects (OD 1000h
+ 1FFFh) and a selected number of manufacturer-specific
objects (frequency converter parameters) in the OD range
2000h–5FFFh.
Danfoss provides a generic English EDS file covering all
voltage and power sizes for off-line configuration.
Download the EDS file from
sAreas/DrivesSolutions/Softwaredownload/
DDFieldbus_Setup_Files.htm
.
NOTICE
The EDS files do not contain all parameters but a
selected, limited number of parameters with generic
minimum, maximum, and default values.
Configuration
VLT
®
CANopen MCA 105
10
Danfoss A/S © 06/2015 All rights reserved.
MG92G102
3
3