7.2 Example: Control Word Telegram Using Standard Telegram 1/PPO3
This example shows how the control word telegram relates to the controller and the frequency converter, using FC control
profile.
The control word telegram is sent from the PLC to the frequency converter. Standard telegram 1 is used in the example to
demonstrate the full range of modules. All the values shown are arbitrary and are provided for demonstration purposes
only.
0
1
2
3
CTW
MRV
PCD
PCD
04
7C
20
00
PQW:
256
258
260
262
CTW
MRV
Bit no.:
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
1
0
0
0
1
1
1
1
1
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
4
7
C
2
0
0
0
Table 7.3 PCD
indicates the bits contained within the control word and how they are presented as process data in standard
telegram 1 in this example.
indicates which bit functions and which corresponding bit values are active in this example.
Bit
Bit value = 0
Bit value = 1
Bit value
00
Reference value
External selection lsb
0
C
01
Reference value
External selection msb
0
02
DC brake
Ramp
1
03
Coasting
Enable
1
04
Quick stop
Ramp
1
7
05
Freeze output
Ramp enable
1
06
Ramp stop
Start
1
07
No function
Reset
0
08
No function
Jog
0
4
09
Ramp 1
Ramp 2
0
10
Data not valid
Valid
1
11
No function
Relay 01 active
0
12
No function
Relay 02 active
0
0
13
Parameter set-up
Selection lsb
0
14
Parameter set-up
Selection msb
0
15
No function
Reversing
0
Function active
–
–
–
Function inactive
–
–
–
Table 7.4 Control Word Telegram Using Standard Telegram 1/PPO3
Application Examples
Programming Guide
MG06G102
Danfoss A/S © 04/2017 All rights reserved.
41
7
7