Input the tension reference in parameter
parameter 37-21 Tension Set Point
•
Set parameter
parameter 37-57 Tension On/Off
to
[1] On
, parameter
parameter 37-59 Diameter Reset
to
[0] Off
, and then initiate a start signal.
Parameter
Value
3-03 Maximum Reference
50
3-41 Ramp 1 Ramp Up Time
0.05
3-42 Ramp 1 Ramp Down Time
0.05
5-30 Terminal 27 Digital Output
[174] TLD indicator
5-31 Terminal 29 Digital Output
[173] End of roll
5-70 Term 32/33 Pulses Per
Revolution
Based on the winder encoder.
5-71 Term 32/33 Encoder
Direction
Based on the winder encoder.
6-10 Terminal 53 Low Voltage
0
6-11 Terminal 53 High Voltage
10
6-14 Terminal 53 Low Ref./
Feedb. Value
0
6-15 Terminal 53 High Ref./
Feedb. Value
100
6-19 Terminal 53 mode
[1] Voltage mode
6-70 Terminal 45 Mode
[2] Digital Output
Parameter 6-72 Terminal 45
Digital Output
[176] Ready to run
6-90 Terminal 42 Mode
[0] 0–20 mA
6-91 Terminal 42 Analog
Output
[162] Tapered tension set point
6-93 Terminal 42 Output Min
Scale
0
6-94 Terminal 42 Output Max
Scale
100
7-00 Speed PID Feedback
Source
[1] 24V encoder
7-07 Speed PID Feedback Gear
Ratio
Based on the application.
17-10 Signal Type
Based on the line encoder.
17-11 Resolution (PPR)
Based on the line encoder.
Parameter 37-00 Application
Mode
[0] Drive mode
Parameter 37-20 Winder Mode
Selection
[0] Wind
Parameter 37-22 Taper Set
Point
0
Parameter 37-23 Partial Roll
Diameter Value
5.000%
Based on the application.
Based on the application.
Parameter 37-26 Winder Jog
Speed
1
0
Parameter 37-28 TLD High Limit
90
1
1
Parameter 37-31 Diameter Limit
Detector
90
Parameter 37-32 Initial
Diameter Measurement
[0] Set diameter when diameter
reset (default)
Parameter 37-33 Diameter
Measurement Input
[0] No function
Parameter 37-34 Reading at
Core
0.00
Parameter 37-35 Reading at
Full Roll
0.00
Parameter 37-36 Tension Set
Point Input
[0] Par.3721
Parameter 37-37 Taper Set
Point Input
[0] Par.3722
Parameter 37-38 Tension
Feedback Input
[1] Input 53(0–10 V DC or 0–20
mA )
Parameter 37-39 Tension
Feedback Type
Based on the application.
Parameter 37-40 Center Winder
Cmd Src
[1] Parameter 19-61–19-67
control the functions
Parameter 37-41 Diameter
Change Rate
0.02
Parameter 37-42 Tapered
Tension Change Rate
0.2
Parameter 37-43 Diameter
Calculator Min Speed
0.5
Parameter 37-44 Line
Acceleration Feed Forward
0
Parameter 37-45 Line Speed
Source
[2] MCB102
Parameter 37-46 Winder Speed
Match Scale
1.000
Parameter 37-47 Tension PID
Profile
Based on the application.
Parameter 37-48 Tension PID
Proportional Gain
Based on the application.
Parameter 37-49 Tension PID
Derivate Time
Based on the application.
Parameter 37-50 Tension PID
Integral Time
Based on the application.
Parameter 37-51 Tension PID
Out Limit
0.00%
Parameter 37-52 Tension PID
Der Gain Limit
Based on the application.
Parameter 37-53 Tension PID
Anti Windup
[1] Enable
Parameter 37-54 Winder Jog
Reverse
0
Parameter 37-55 Winder Jog
Forward
0
Parameter 37-56 New Diameter
Select
[0] Core Diameter
Center Winder Control
VLT
®
AutomationDrive FC 360
10
Danfoss A/S © 11/2014 All rights reserved.
MG06E102