37-49 Tension PID Derivate Time
Sets the derivative time for tension loop PID amplifier.
Range:
Function:
0 s
*
[0 - 20 s]
37-50 Tension PID Integral Time
Sets the integral time for tension loop PID amplifier.
Range:
Function:
501 s
*
[0.01 - 501 s]
37-51 Tension PID Out Limit
Sets the maximum tension PID loop output that can be added to
the open loop speed reference. The value is normally set to limit
the contribution of the tension PID loop to 10 % of the
maximum reference speed.
Range:
Function:
0 %
*
[0 - 100 %]
37-52 Tension PID Der Gain Limit
Sets the limit for derivation gain in tension loop PID amplifier.
Range:
Function:
5
*
[1 - 50 ]
37-53 Tension PID Anti Windup
Activates the anti-wind-up function in tension loop PID amplifier.
Option:
Function:
[0]
Disabled
[1]
*
Enabled
37-54 Winder Jog Reverse
Jogs the winder in the reverse winding direction at the speed set
in
parameter 37-26 Winder Jog Speed
Option:
Function:
[0]
*
No Function
[1]
Jog reverse
37-55 Winder Jog Forward
Jogs the winder in forward winding direction at the speed set in
parameter 37-26 Winder Jog Speed
.
Option:
Function:
[0]
*
No function
[1]
Jog forward
37-56 New Diameter Select
Selects partial roll diameter as the preset starting diameter when
the diameter reset is energized, rather than using one of the 2
preset core diameters.
Option:
Function:
[0]
*
Core diameter
[1]
Partial roll diameter
37-57 Tension On/Off
Turns the tension controller on or off.
Option:
Function:
[0]
*
Off
[1]
On
37-58 Core Select
Selects 1 of the 2 preset core sizes.
Option:
Function:
[0]
*
Core1 diameter
[1]
Core2 diameter
37-59 Diameter Reset
Resets the diameter to a new value. If the new diameter select is
energized, the partial core diameter value is used, otherwise the
diameter is reset to core1 or core2 values based on the selected
core.
Option:
Function:
[0]
*
Off
[1]
On
Center Winder Control
Application Guide
MG06E102