0-51 Set-up Copy
Option:
Function:
[4]
Copy to set-
up 4
Copies all parameters in the present
programming set-up (defined in
) to set-up 4.
[9]
Copy to all
Copies the parameters in the present set-up
to each of the set-ups 1 to 4.
3.1.7 0-6* Password
0-60 Main Menu Password
Range:
Function:
100
*
[-9999 -
9999 ]
Define the password for access to the Main
Menu via the [Main Menu] key. If
parameter 0-61 Access to Main Menu w/o
Password
is set to
[0] Full access
, this
parameter is ignored.
0-61 Access to Main Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in
parameter 0-60 Main Menu Password
[1]
LCP: Read
only
Prevent unauthorized editing of
Main Menu
parameters.
[2]
LCP: No
access
Prevent unauthorized viewing and editing of
Main Menu
parameters.
[3]
Bus: Read
only
Read-only functions for parameters on
fieldbus and/or FC standard bus.
[4]
Bus: No
access
No access to parameters is allowed via
fieldbus and/or FC standard bus.
[5]
All: Read only Read-only function for parameters on LCP,
fieldbus, or FC standard bus.
[6]
All: No access No access from LCP, fieldbus, or FC standard
bus is allowed.
If
[0] Full access
is selected,
parameter 0-65 Personal Menu Password
, and
parameter 0-66 Access to Personal Menu w/o Password
are
ignored.
NOTICE
A more complex password protection is available for
OEMs upon request.
0-65 Personal Menu Password
Range:
Function:
200
*
[-9999 -
9999 ]
Define the password for access to the Quick
Menu via the [Quick Menu] key. If
parameter 0-66 Access to Personal Menu w/o
Password
is set to
[0] Full access
, this
parameter is ignored.
0-66 Access to Personal Menu w/o Password
If
parameter 0-61 Access to Main Menu w/o Password
is set to
[0]
Full access
, then this parameter is ignored.
Option:
Function:
[0]
*
Full access
Disables the password defined in
parameter 0-65 Personal Menu Password
.
[1]
LCP: Read only Prevents unauthorized editing of
Quick
Menu
parameters.
[3]
Bus: Read only Read-only functions for
Quick Menu
parameters on fieldbus and/or FC standard
bus.
[5]
All: Read only
Read-only function for
Quick Menu
parameters on LCP, fieldbus, or frequency
converter standard bus.
0-67 Bus Password Access
Range:
Function:
0
*
[0 - 9999 ] Use this parameter to unlock the frequency
converter via fieldbus or MCT 10 Set-up
Software.
0-68 Safety Parameters Password
Range:
Function:
300
*
[0 -
9999 ]
Enter the password for the safety parameters
access. If
parameter 0-69 Password Protection of
Safety Parameters
is set to
[0] Disabled
, this
parameter is ignored.
0-69 Password Protection of Safety Parameters
Option:
Function:
[0]
*
Disabled
[1]
Enabled
0-70 Date and Time
Range:
Function:
Size
related
*
[ 0 -
0 ]
Sets the date and time of the internal clock.
The format to be used is set in
parameter 0-71 Date Format
and
parameter 0-72 Time Format
.
When using the
VLT
®
Real-time Clock MCB
117
option, the time is synchronized at 15:00
every day.
0-73 Time Zone Offset
Range:
Function:
0 min
*
[-780 - 780
min]
Enter the time zone offset relative to
UTC. This parameter is required for the
automatic daylight saving time
adjustment.
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
40
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3