13-51 SL Controller Event
Option:
Function:
[223] On Target
NOTICE
This option is available only with
software version 48.20 and
newer.
Positioning is completed and the on-
target signal is sent when the actual
position is within
for the duration of
and the
actual speed does not exceed
parameter 3-05 On Reference Window
[224] Position Error
NOTICE
This option is available only with
software version 48.20 and
newer.
The position error exceeds the value
in
parameter 4-71 Maximum Position
for the time set in
parameter 4-72 Position Error Timeout
.
[225] Position Limit
NOTICE
This option is available only with
software version 48.20 and
newer.
The position is outside the limits set
in
parameter 3-06 Minimum Position
and
parameter 3-07 Maximum Position
.
[226] Touch on Target
NOTICE
This option is available only with
software version 48.20 and
newer.
Target position is reached in touch
probe position mode.
[227] Touch Activated
NOTICE
This option is available only with
software version 48.20 and
newer.
Touch probe positioning active. The
frequency converter monitors the
touch probe sensor input.
13-52 SL Controller Action
Option:
Function:
Select the action corresponding to the SLC
event. Actions are executed when the
corresponding event (defined in
13-52 SL Controller Action
Option:
Function:
parameter 13-51 SL Controller Event
) is
evaluated as true.
[0]
DISABLED
[1]
No action
[2]
Select set-up
1
Changes the active set-up
(
parameter 0-10 Active Set-up
) to 1.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a fieldbus.
[3]
Select set-up
2
Changes the active set-up
parameter 0-10 Active Set-up
) to 2.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a fieldbus.
[4]
Select set-up
3
Changes the active set-up
(
parameter 0-10 Active Set-up
) to 3.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a fieldbus.
[5]
Select set-up
4
Changes the active set-up
(
parameter 0-10 Active Set-up
) to 4.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a fieldbus.
[10]
Select preset
ref 0
Selects preset reference 0.
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[11]
Select preset
ref 1
Selects preset reference 1.
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[12]
Select preset
ref 2
Selects preset reference 2.
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[13]
Select preset
ref 3
Selects preset reference 3.
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[14]
Select preset
ref 4
Selects preset reference 4.
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[15]
Select preset
ref 5
Selects preset reference 5.
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
186
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3