13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
[0] DISABLED
Ignores:
•
Parameter 13-42 Logic Rule Boolean 2
.
•
Parameter 13-43 Logic Rule Operator 2
•
Parameter 13-44 Logic Rule Boolean 3
.
[1] AND
Evaluates the expression [13-40] AND [13-42].
[2] OR
Evaluates the expression [13-40] OR [13-42].
[3] AND NOT
Evaluates the expression [13-40] AND NOT
[13-42].
[4] OR NOT
Evaluates the expression [13-40] OR NOT
[13-42].
[5] NOT AND
Evaluates the expression NOT [13-40] AND
[13-42].
[6] NOT OR
Evaluates the expression NOT [13-40] OR
[13-42].
[7] NOT AND
NOT
Evaluates the expression NOT [13-40] AND NOT
[13-42].
[8] NOT OR
NOT
Evaluates the expression NOT [13-40] OR NOT
[13-42].
3.13.7 13-42 Logic Rule Boolean 2
13-42 Logic Rule Boolean 2
Option:
Function:
[0]
False
Select the 2
nd
boolean (true or false)
input for the selected logic rule. See
parameter 13-01 Start Event
and
parameter 13-02 Stop Event
for more
information.
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed
range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb.
range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
13-42 Logic Rule Boolean 2
Option:
Function:
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
[41]
Reset Trip
[42]
Auto-reset Trip
[43]
Ok key
[OK] is pressed. Only available on the
graphical LCP.
[44]
Reset key
[Reset] is pressed. Only available on
the graphical LCP.
[45]
Left key
[
◄
] is pressed. Only available on the
graphical LCP.
[46]
Right key
[
►
] is pressed. Only available on the
graphical LCP.
[47]
Up key
[
▲
] is pressed. Only available on the
graphical LCP.
[48]
Down key
[
▼
] is pressed. Only available on the
graphical LCP.
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[75]
Start command
given
[76]
Digital input x30/2
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
180
Danfoss A/S © 10/2018 All rights reserved.