8-52 DC Brake Select
Select control of the DC brake via the terminals (digital input)
and/or via the fieldbus.
Option:
Function:
[3] Logic OR
Activate a start command via the fieldbus/serial
communication port or via 1 of the digital
inputs.
8-53 Start Select
Select the trigger for the start function.
Option:
Function:
[0]
Digital input A digital input triggers the start function.
[1]
Bus
A serial communication port or the fieldbus
triggers the start function.
[2]
Logic AND
The fieldbus/serial communication port and a
digital input trigger the start function.
[3]
*
Logic OR
The fieldbus/serial communication port or a
digital input triggers the start function.
8-54 Reversing Select
Select the trigger for the reversing function.
Option:
Function:
[0] Digital input A digital input triggers the reversing function.
[1] Bus
A serial communication port or the fieldbus
triggers the reversing function.
[2] Logic AND
The fieldbus/serial communication port and a
digital input trigger the reversing function.
[3] Logic OR
The fieldbus/serial communication port or a
digital input triggers the reversing function.
8-55 Set-up Select
Select the trigger for the set-up selection.
Option:
Function:
[0]
Digital input A digital input triggers the set-up selection.
[1]
Bus
A serial communication port or the fieldbus
triggers the set-up selection.
[2]
Logic AND
The fieldbus/serial communication port and a
digital input trigger the set-up selection.
[3]
*
Logic OR
The fieldbus/serial communication port or a
digital input triggers the set-up selection.
8-56 Preset Reference Select
Option:
Function:
Select the trigger for the preset reference
selection.
[0]
Digital
input
A digital input triggers the preset reference
selection.
[1]
Bus
A serial communication port or the fieldbus
triggers the preset reference selection.
8-56 Preset Reference Select
Option:
Function:
[2]
Logic AND
The fieldbus/serial communication port and a
digital input trigger the preset reference
selection.
[3]
*
Logic OR
The fieldbus/serial communication port or a
digital input triggers the preset reference
selection.
8-57 Profidrive OFF2 Select
Select control of the frequency converter OFF2 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
is set to
[0] Digital
and ctrl. word
and
parameter 8-10 Control Word Profile
is set to
[1]
PROFIdrive profile
.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-58 Profidrive OFF3 Select
Select control of the frequency converter OFF3 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
parameter 8-01 Control Site
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1]
PROFIdrive profile
.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
3.9.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus
communication via the frequency converter port.
8-80 Bus Message Count
Range:
Function:
0
*
[0 - 0 ] This parameter shows the number of valid
telegrams detected on the bus.
8-81 Bus Error Count
Array [6]
Range:
Function:
0
*
[0 - 0 ] This parameter shows the number of telegrams
with faults (for example CRC fault) detected on the
bus.
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
164
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3