6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise in
terminal 54. Increasing the value improves
dampening but also increases the time
delay through the filter.
3.7.4 6-3* Analog Input 3 General Purpose
I/O MCB 101
Parameter group for configuring the scale and limits for
analog input 3 (X30/11) in VLT
®
General Purpose I/O MCB
101.
6-30 Terminal X30/11 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par.
6-31 V]
Sets the analog input scaling value to
correspond to the low reference feedback
value (set in
).
6-31 Terminal X30/11 High Voltage
Range:
Function:
10 V
*
[ par. 6-30 -
10 V]
Sets the analog input scaling value to
correspond to the high reference feedback
value (set in
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Sets the analog input
scaling value to
correspond to the low
voltage value (set in
parameter 6-30 Terminal
X30/11 Low Voltage
).
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Sets the analog input scaling
value to correspond to the
high-voltage value (set in
parameter 6-31 Terminal X30/11
High Voltage
6-36 Term. X30/11 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This
constant is a first-order digital low-pass
filter time for suppressing electrical noise
in terminal X30/11. A high value improves
dampening but also increases the delay
through the filter.
3.7.5 6-4* Analog Input X30/12
Parameter group for configuring the scale and limits for
analog input 4 (X30/12) in VLT
®
General Purpose I/O MCB
101.
6-40 Terminal X30/12 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par.
6-41 V]
Sets the analog input scaling value to
correspond to the low reference feedback
value set in
6-41 Terminal X30/12 High Voltage
Range:
Function:
10 V
*
[ par. 6-40 -
10 V]
Sets the analog input scaling value to
correspond to the high reference feedback
value set in
.
6-44 Term. X30/12 Low Ref./Feedb. Value
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Sets the analog output
scaling value to
correspond to the low
voltage value set in
parameter 6-40 Terminal
X30/12 Low Voltage
6-45 Term. X30/12 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Sets the analog input scaling
value to correspond to the high
voltage value set in
parameter 6-41 Terminal X30/12
High Voltage
.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
137
3
3
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......