NOTICE
Thermistors may be connected to either an analog or a
digital input.
6-00 Live Zero Timeout Time
Range:
Function:
10
s
*
[0 -
99 s]
Enter the live zero timeout in s. Live zero timeout
time is active for analog inputs, that is terminal 53
or terminal 54, used as reference or feedback
sources.
If the reference signal value associated with the
selected current input drops below 50% of the
value set in:
•
Parameter 6-10 Terminal 53 Low Voltage
•
Parameter 6-12 Terminal 53 Low Current
•
Parameter 6-20 Terminal 54 Low Voltage
•
Parameter 6-22 Terminal 54 Low Current
for a time period longer than the time set in
parameter 6-00 Live Zero Timeout Time
, the function
selected in
parameter 6-01 Live Zero Timeout
is activated.
6-01 Live Zero Timeout Function
Option:
Function:
Select the timeout function. If the input signal
on terminal 53 or 54 is below 50% of the value
in
•
Parameter 6-10 Terminal 53 Low Voltage
•
Parameter 6-12 Terminal 53 Low Current
•
Parameter 6-20 Terminal 54 Low Voltage
•
Parameter 6-22 Terminal 54 Low Current
for a time period defined in
, then the function set in
parameter 6-01 Live Zero Timeout Function
is
activated.
If several timeouts occur simultaneously, the
frequency converter prioritizes the timeout
functions as follows:
1.
Parameter 6-01 Live Zero Timeout
Function
.
2.
Parameter 8-04 Control Word Timeout
Function
.
[0]
*
Off
[1]
Freeze
output
Frozen at the present value.
[2]
Stop
Overruled to stop.
[3]
Jogging
Overruled to jog speed.
[4]
Max.
speed
Overruled to maximum speed.
[5]
Stop and
trip
Overruled to stop with subsequent trip.
6-01 Live Zero Timeout Function
Option:
Function:
[20] Coast
[21] Coast and
trip
3.7.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog
input 1 (terminal 53).
Ex.
5 V
10 V
300
600
900
1200
1500
150
130B
T103.10
1 V
Par 6-xx
'Low Voltage'or
'Low Current'
Par 6-xx
'High Voltage'or
'High Current'
Analog input
Ref./Feedback
[RPM]
Par 6-xx
'High Ref./
Feedb. Value'
Par 6-xx
'Low Ref./
Feedb. Value'
Illustration 3.43 Analog Input 1
6-10 Terminal 53 Low Voltage
Range:
Function:
Size
related
*
[ -10.00 -
par. 6-11 V]
Enter the low voltage value. This
analog input scaling value should
correspond to the minimum reference
value set in
6-11 Terminal 53 High Voltage
Range:
Function:
10 V
*
[ par. 6-10
- 10 V]
Enter the high voltage value. This analog
input scaling value should correspond to the
high reference feedback value set in
parameter 6-15 Terminal 53 High Ref./Feedb.
Value
.
6-12 Terminal 53 Low Current
Range:
Function:
0.14
mA
*
[ 0 -
par. 6-13
mA]
Enter the low current value. This reference
signal should correspond to the minimum
reference value, set in
parameter 3-02 Minimum Reference
. Set the
value to exceed 2 mA in order to activate the
live zero timeout function in
parameter 6-01 Live Zero Timeout Function
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
135
3
3