5-78 Term 27/29 Encoder Sim
Option:
Function:
parameter 3-22 Master Scale Numerator
parameter 3-23 Master Scale Denominator
parameter 17-72 Position Unit Numerator
and
parameter 17-73 Position Unit Denominator
3.6.8 5-8* I/O Options
5-80 AHF Cap Reconnect Delay
Range:
Function:
25 s
*
[1 - 120
s]
Guarantees a minimum off-time for the
capacitors. The timer starts once the AHF
capacitor disconnects and has to expire before
the output is allowed to be on again. It only
turns on again if the frequency converter
power is 20–30%.
3.6.9 5-9* Bus-controlled
This parameter group selects digital and relay outputs via a
fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0
*
[0 - 2147483647 ] This parameter holds the state of the
digital outputs and relays that is
controlled by bus.
A logical 1 indicates that the output is
high or active.
A logical 0 indicates that the output is
low or inactive.
Bit 0
Digital output terminal 27
Bit 1
Digital output terminal 29
Bit 2
Digital output terminal X 30/6
Bit 3
Digital output terminal X 30/7
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6
Option B relay 1 output terminal
Bit 7
Option B relay 2 output terminal
Bit 8
Option B relay 3 output terminal
Bit 9–15
Reserved for future terminals
Bit 16
Option C relay 1 output terminal
Bit 17
Option C relay 2 output terminal
Bit 18
Option C relay 3 output terminal
Bit 19
Option C relay 4 output terminal
Bit 20
Option C relay 5 output terminal
Bit 21
Option C relay 6 output terminal
Bit 22
Option C relay 7 output terminal
Bit 23
Option C relay 8 output terminal
Bit 24–31
Reserved for future terminals
Table 3.22 Bus-controlled Digital Outputs and Relays
5-93 Pulse Out #27 Bus Control
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to
output terminal 27 when the terminal is
configured as
[45] Bus Controlled
in
parameter 5-60 Terminal 27 Pulse Output
Variable
.
5-94 Pulse Out #27 Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to output
terminal 27 when the terminal is configured as
[48] Bus Ctrl Timeout
in
and a timeout is
detected.
5-95 Pulse Out #29 Bus Control
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to
output terminal 29 when the terminal is
configured as
[45] Bus Controlled
in
parameter 5-63 Terminal 29 Pulse Output
Variable
.
5-96 Pulse Out #29 Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to output
terminal 29 when the terminal is configured as
[48] Bus Ctrl Timeout
in
and a timeout is
detected.
5-97 Pulse Out #X30/6 Bus Control
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to
output terminal X30/6 when the terminal is
configured as
[45] Bus ctrl.
in
parameter 5-66 Terminal X30/6 Pulse Output
Variable
.
5-98 Pulse Out #X30/6 Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to output
terminal X30/6 when the terminal is configured
as
[48] Bus Ctrl Timeout
in
parameter 5-66 Terminal X30/6 Pulse Output
Variable
and a timeout is detected.
3.7 Parameters: 6-** Analog In/Out
3.7.1 6-0* Analog I/O Mode
The analog inputs can be allocated to be either voltage
(FC 301: 0–10 V, FC 302: 0 to
±
10 V) or current input (FC
301/FC 302: 0/4–20 mA).
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
134
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3