Frame size
Bussmann PN
Rating
D, E, F
FNQ-R-3
3 A, 600 V
Table 11.20 Transformer Fuse (Line Contactor)
Frame size
Bussmann PN
Rating
D, E, F
FNQ-R-1
1 A, 600 V
Table 11.21 Soft Charge Fuses
11.6 General Torque Tightening Values
For fastening hardware described in this manual, use the torque values in
. These values are not intended for
fastening IGBTs. See the instructions included with those replacement parts for correct values.
Shaft Size
Driver Size Torx/Hex [mm]
Torque [Nm]
Torque [in-lbs]
M4
T-20/7
1.0
10
M5
T-25/8
2.3
20
M6
T-30/10
4.0
35
M8
T-40/13
9.6
85
M10
T-50/17
19.2
170
M12
18/19
19
170
Table 11.22 Torque Values
Specifications
Instruction Manual
MG37A222
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
167
11
11