FC 302 with MCO - mains connectors and 4 cable glands
(134N8410)
Illustration 3.3 Mains Connectors and 4 Cable Glands
FC 302 with connectors - side view
Illustration 3.4 Side View
NOTICE
See the
VLT
®
AutomationDrive FC 301/FC 302 Design Guide
for dimensions and further information.
Connectors
Overview
The frequency converter has 7 connectors plus 2 or 4 motor
connectors.
Label
Connector
Description
X1
Mains
Mains in M23 (in M25) Male
X2.1-X2.4
Motor
Motor connection M23 Female
X51
PROFIBUS - Male
PROFIBUS M12
X52
PROFIBUS - Female PROFIBUS M12
X11-X14
I/O box connector
Phoenix I/O box
Table 4.1 Connectors
X1- Mains M23 (in M25) Male
General ratings
•
Pins 1, 2, 3, and 4: 480 V AC, maximum 15 A.
•
Pins C and D: 30 V DC, maximum 3 A.
•
Tightening torque: 1.5–2.0 Nm (13.3–17.7 in-lb)
Pin
Label
Connected to frequency
converter wiring schematic
Minimum
wire [mm
2
(AWG)]
1
T1
91 (L1)
2.5 (14)
4
T2
92 (L2)
2.5 (14)
3
T3
93 (L3)
2.5 (14)
2
PE
95 (PE)
2.5 (14)
D
0 V DC
35
0.75 (18)
C
24 V DC
36
0.75 (18)
Table 4.2 Wire/Connector Assignment for Plug X1
Mating part: Mains X1 (female)
Phoenix ordering number: KK-0885/XX,XX
Installation Instructions
VLT® AutomationDrive FC 302 with Connectors
2
Danfoss A/S © 11/2015 All rights reserved.
MI04G402