Option
Function
[90]
kWh counter pulse
Sends a pulse (200 ms pulse width) to output terminal whenever kWh counter changes (
parameter
15-02 kWh Counter
).
[90]
kWh counter pulse
N O T I C E
This option is only available with software version 48.XX.
Sends a pulse (200 ms pulse width) to the output terminal whenever kWh counter changes (
pa-
rameter 15-02 kWh Counter
).
[98]
Virtual master dir.
N O T I C E
This option is only available with software version 48.XX.
A virtual master signal that controls the rotation direction of followers.
[120] Local ref active
Output is high when
parameter 313 Reference Site
=
[2] Local
.
Table 354: Local Reference Active
Reference site set in
parameter 3-13 Reference Site
Local reference active [120]
Remote reference active [121]
Reference site: Local
parameter 3-13 Reference Site [2] Local
1
0
Reference site: Remote
parameter 3-13 Reference Site [1] Remote
0
1
Reference site: Linked to Hand/ Auto
–
–
Hand
1
0
Hand
⇒
off
1
0
Auto
⇒
off
0
0
Auto
0
1
Table 355: 5-30 Digital Outputs - 2
Option
Function
[121] Remote ref active
Output is high when
parameter 3-13 Reference Site
=
[1] Remote
or
[0] Linked to hand/auto
while
the LCP is in auto-on mode. See
.
[122] No alarm
Output is high when no alarm is present.
[123] Start command ac-
tive
Output is high when there is an active start command (that is via digital input bus connection,
hand-on, or auto-on), and no stop or start command is active.
[124] Running reverse
Output is high when the drive runs counterclockwise (the logical product of the status bits run-
ning AND reverse).
[125] Drive in hand mode
Output is high when the drive is in hand-on mode (as indicated by the LED light above [Hand
On]).
[126] Drive in auto mode
Output is high when the drive is in auto-on mode (as indicated by the LED light above [Auto On]).
[151] ATEX ETR cur. alarm
Selectable if
parameter 1-90 Motor Thermal Protection
is set to
[20] ATEX ETR
or
[21] Advanced ETR
. If
Alarm 164 ATEX ETR cur.lim.alarm
is active, the output is 1.
AU275636650261en-000101 / 130R0334
202 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide