130BD531.10
U
V
W
96
97
98
Illustration 4.5 Motor Connection
shows mains input, motor, and grounding
for basic frequency converters. Actual configurations vary
with unit types and optional equipment.
95
130BB920.10
+DC
BR-
B
M
A
I
N
S
L1 L2 L3
91 92 93
RELA
Y 1 RELA
Y 2
99
- LC -
U V
W
MO
TOR
99
Illustration 4.6 Example of Motor, Mains, and Ground Wiring
4.7 AC Mains Connection
•
Size the wiring based on the input current of the
frequency converter. For maximum wire sizes, see
•
Comply with local and national electrical codes
for cable sizes.
Procedure
1.
Connect the 3-phase AC input power wiring to
terminals L1, L2, and L3 (see
).
2.
Depending on the configuration of the
equipment, connect the input power to the
mains input terminals or the input disconnect.
3.
Ground the cable in accordance with the
grounding instructions provided in
4.
When supplied from an isolated mains source (IT
mains or floating delta) or TT/TN-S mains with a
grounded leg (grounded delta), ensure that
parameter 14-50 RFI Filter
is set to
[0] Off
to avoid
damage to the DC link and to reduce ground
capacity currents in accordance with IEC 61800-3.
4.8 Control Wiring
•
Isolate the control wiring from the high-power
components in the frequency converter.
•
When the frequency converter is connected to a
thermistor, ensure that the thermistor control
wiring is screened and reinforced/double
insulated. A 24 V DC supply voltage is
recommended. See
4.8.1 Control Terminal Types
and
show the removable
frequency converter connectors. Terminal functions and
default settings are summarised in
and
.
2
3
4
1
130BB921.11
Illustration 4.7 Control Terminal Locations
Electrical Installation
Operating Instructions
MG33AQ02
Danfoss A/S © 07/2015 All rights reserved.
17
4
4