Auto
on
Reset
Hand
on
Off
Back
Canc
el
In
fo
OK
On
Alarm
Warn.
130BB467.10
Figure 8.3
Warning LED
Alarm LED
Warning
On
Off
Alarm
Off
On (Flashing)
Trip Lock
On
On (Flashing)
Table 8.1
8.4 Warning and Alarm Definitions
defines whether a warning is issued prior to an
alarm, and whether the alarm trips the unit or trip locks
the unit.
No.
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter Reference
1
10 Volts low
X
2
Live zero error
(X)
(X)
6-01 Live Zero Timeout
Function
4
Mains phase loss
(X)
(X)
(X)
14-12 Function at Mains
Imbalance
5
DC link voltage high
X
6
DC link voltage low
X
7
DC overvoltage
X
X
8
DC undervoltage
X
X
9
Inverter overloaded
X
X
10
Motor ETR overtemperature
(X)
(X)
1-90 Motor Thermal Protection
11
Motor thermistor overtemperature
(X)
(X)
1-90 Motor Thermal Protection
12
Torque limit
X
X
13
Overcurrent
X
X
X
14
Ground fault
X
X
X
15
Hardware mismatch
X
X
16
Short-circuit
X
X
17
Control word timeout
(X)
(X)
8-04 Control Timeout Function
20
Temp. Input Error
21
Param Error
22
Hoist Mech. Brake
(X)
(X)
Parameter Group 2-2*
23
Internal Fans
X
24
External Fans
X
14-53 Fan Monitor
25
Brake resistor short-circuited
X
26
Brake resistor power limit
(X)
(X)
2-13 Brake Power Monitoring
Warnings and Alarms
VLT
®
Automation Drive D-Frame
Instruction Manual
8-2
MG34U222 - VLT
®
is a registered Danfoss trademark
8
8