4-39 Tracking Error After Ramping Timeout
Range:
Function:
5.00 s
*
[0.00 - 60.00 s] Enter the time-out period after ramping
where
and
4-38 Tracking Error Ramping Timeout
are
still active.
3.6.3 4-5* Adjustable Warnings
Use these parameters to adjust warning limits for current,
speed, reference and feedback. Warnings that are shown
on the display can be programmed as an output or sent
via serial bus.
Warnings are shown on display, programmed output or
serial bus.
130BA064.10
(P 4-18)
(P 4-51)
(P 4-50)
(P 4-11)
(P 4-53)
(P 4-52)
(P 4-13)
I
HIGH
I
LOW
n
LOW
n
HIGH
n
motor
I
motor
REF
ON REF
IN RANGE
I
LIM
n
MAX
n
MIN
[RPM]
Illustration 3.32 Adjustable Warnings
4-50 Warning Current Low
Range:
Function:
0.00 A
*
[ 0.00 -
par. 4-51
A]
Enter the I
LOW
value. When the motor
current falls below this limit, the display
reads
Current Low
. The signal outputs can
be programmed to produce a status signal
on terminal 27 or 29 (FC 302 only) and on
relay output 01 or 02 (FC 302 only). Refer to
.
4-51 Warning Current High
Range:
Function:
Size
related
*
[ par.
4-50 - par.
16-37 A]
Enter the I
HIGH
value. When the motor
current exceeds this limit, the display
reads
Current High
. The signal outputs
can be programmed to produce a status
signal on terminal 27 or 29 (FC 302 only)
and on relay output 01 or 02 (FC 302
only). Refer to
4-52 Warning Speed Low
Range:
Function:
0 RPM
*
[ 0 - par.
4-53 RPM]
Enter the n
LOW
value. When the motor
speed exceeds this limit, the display reads
Speed Low
. The signal outputs can be
programmed to produce a status signal on
terminal 27 or 29 (FC 302 only) and on
relay output 01 or 02 (FC 302 only).
4-53 Warning Speed High
Range:
Function:
Size related
*
[ par. 4-52 - par. 4-13 RPM]
4-54 Warning Reference Low
Range:
Function:
-999999.999
*
[ -999999.999 -
par. 4-55 ]
Enter the lower reference limit.
When the actual reference falls
below this limit, the display
indicates
Ref
LOW
. The signal
outputs can be programmed to
produce a status signal on
terminal 27 or 29 (FC 302 only)
and on relay output 01 or 02
(FC 302 only).
4-55 Warning Reference High
Range:
Function:
999999.999
*
[ par. 4-54 -
999999.999 ]
Enter the upper reference limit.
When the actual reference
exceeds this limit, the display
reads Ref High. The signal
outputs can be programmed to
produce a status signal on
terminal 27 or 29 (FC 302 only)
and on relay output 01 or 02 (FC
302 only).
4-56 Warning Feedback Low
Range:
Function:
-999999.999
ReferenceFeed-
backUnit
*
[ -999999.999 -
par. 4-57
ReferenceFeed-
backUnit]
Enter the lower feedback
limit. When the feedback
falls below this limit, the
display reads Feedb Low.
The signal outputs can
be programmed to
produce a status signal
on terminal 27 or 29 (FC
302 only) and on relay
output 01 or 02 (FC 302
only).
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
69