3.21.3 35-2* Temp. Input X48/7 (MCB 114)
35-24 Term. X48/7 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/7. A high time constant
value improves dampening but also
increases the time delay through the
filter.
35-25 Term. X48/7 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/7. The temperature limits
can be set in
35-26 Term. X48/7 Low Temp. Limit
and
Option:
Function:
[0]
*
Disabled
[1]
Enabled
35-26 Term. X48/7 Low Temp. Limit
Range:
Function:
Size related
*
[ -50. - par.
35-27 ]
Enter the minimum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/7.
35-27 Term. X48/7 High Temp. Limit
Range:
Function:
Size related
*
[ par. 35-26 -
204. ]
Enter the maximum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/7.
3.21.4 35-3* Temp. Input X48/10 (MCB 114)
35-34 Term. X48/10 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/10. A high time constant
value improves dampening but also
increases the time delay through the
filter.
35-35 Term. X48/10 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/10. The temperature limits
can be set in
35-36 Term. X48/10 Low Temp. Limit
Option:
Function:
[0]
*
Disabled
[1]
Enabled
35-36 Term. X48/10 Low Temp. Limit
Range:
Function:
Size related
*
[ -50. - par.
35-37 ]
Enter the minimum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/10.
35-37 Term. X48/10 High Temp. Limit
Range:
Function:
Size related
*
[ par. 35-36 -
204. ]
Enter the maximum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/10.
3.21.5 35-4* Analog Input X48/2 (MCB 114)
35-42 Term. X48/2 Low Current
Range:
Function:
4.00
mA
*
[ 0.00 -
par. 35-43
mA]
Enter the current (mA) that corresponds
to the low reference value, set in
35-44 Term. X48/2 Low Ref./Feedb. Value
The value must be set at >2 mA in order
to activate the Live Zero Time-out
Function in
.
35-43 Term. X48/2 High Current
Range:
Function:
20.00 mA
*
[ par. 35-42 -
20.00 mA]
Enter the current (mA) that
corresponds to the high reference
value (set in
35-44 Term. X48/2 Low Ref./Feedb. Value
Range:
Function:
0.000
*
[-999999.999 -
999999.999 ]
Enter the reference or feedback
value (in RPM, Hz, bar, etc.) that
corresponds to the voltage or
current set in
.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
157