Option
Name
Description
[0]
Disabled
[1]*
Enabled
[2]
Password
Parameter 0-45 [Drive Bypass] Key on LCP
Table 35: Parameter 0-45 [Drive Bypass] Key on LCP
0-45 [Drive Bypass] Key on LCP
Default value: [1] Enabled
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Press [Off] and select
[0] Disabled
to avoid unintended stop of the drive. Press [Off] and select
[2] Password
to avoid unauthorized
bypass of the drive. If
parameter 0-45 [Drive Bypass] Key on LCP
is included in the Quick Menu, define the password in
parameter 0-65
Personal Menu Password
.
Option
Name
Description
[0]
Disabled
Disables the key.
[1]*
Enabled
[2]
Password
4.1.6 0-5* Copy/Save
Copy parameters from and to the LCP. Use these parameters for saving and copying setups from 1 drive to another.
Parameter 0-50 LCP Copy
Table 36: Parameter 0-50 LCP Copy
0-50 LCP Copy
Default value: [0] No copy
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
Option Name
Description
[0]*
No copy
[1]
All to LCP
Copies all parameters in all set-ups from the drive memory to the LCP memory.
[2]
All from LCP
Copies all parameters in all set-ups from the LCP memory to the drive memory.
[3]
Size indep. from LCP
Copy only the parameters that are independent of the motor size. This selection can be used
to program several drives with the same function without disturbing motor data.
[6]
Data from DYN to LCP
[7]
Data from LCP to DYN
[10]
Delete LCP copy data
Use to delete the copy after the transfer is complete.
AU373327181955en-000101 / 130R1208
50 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide