Option Name
Description
[0]*
Log always
Select
[0] Log always
for continuous logging.
[1]
Log once on trigger Select
[1] Log once on trigger
to start and stop logging conditionally using
parameter 15-12 Trig-
ger Event
and
parameter 15-14 Samples Before Trigger
.
Parameter 15-14 Samples Before Trigger
Table 533: Parameter 15-14 Samples Before Trigger
15-14 Samples Before Trigger
Default Value: 50
Parameter Type: Range, 0 - 100
Setup: 2 set-ups
Conversion Index: 0
Data Type: Uint8
Change during operation: True
Before a trigger event, enter the percentage of all samples which should be retained in the log. See also
parameter 15-12 Trigger
Event
and
parameter 15-13 Logging Mode
.
Parameter 15-15 Info Message: "Service Log Full"
Table 534: Parameter 15-15 Info Message: "Service Log Full"
15-15 Info Message: "Service Log Full"
Default Value: [0] Disabled
Parameter Type: Option
Setup: 1 set-up
Conversion Index: -
Data Type: Uint8
Change during operation: True
See Service log. By enabling this parameter, a text message is shown in the drive when the service log runs full:
Clear logs, Service log
full: 28 [M26]
. The message recommends to clear the log.
Option
Name
Description
[0]*
Disabled
[1]
Enabled
Enable message,
4.15.3 Service Log
The service log function saves detailed log information of a 5-second interval when alarms occur. Service technicians can analyze
this information to troubleshoot and optimize the drive.
The drive can save up to 24 service log records in the flash memory.
Find the list of alarms that trigger a service log record in
4.15.7 Alarms that Trigger a Service Log Record
. Application-dependent
trips/alarms, for example, Safe Torque Off, do not trigger a service log record.
Sampling rate
There are 2 periods with different sampling rates:
Slow samples: 20 samples at a rate of 250 ms resulting in 5 s of history before the trip.
Fast samples: 50 samples at a rate of 5 ms resulting in 250 ms of detailed history before the trip.
N O T I C E
To enable the real-time clock (RTC) stamp, use the real-time clock module. If real-time clock is not available, the operating time in
parameter 15-32 Fault Log: Time
is recorded.
Table 535: Service Log Data
#
Alarm log data
Parameter
1
Time of trip (1 of the values):
Parameter 0-89 Date and Time Readout
or
parameter 15-32 Fault Log:
Time
AU373327181955en-000101 / 130R1208
290 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide