Parameter 6-14 Terminal 53 Low Ref./Feedb. Value
Table 349: Parameter 6-14 Terminal 53 Low Ref./Feedb. Value
6-14 Terminal 53 Low Ref./Feedb. Value
Default value: Size related Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the analog input scaling value that corresponds to the low voltage/low current set in
parameter 6-10 Terminal 53 Low Voltage
and
parameter 6-12 Terminal 53 Low Current
.
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
Table 350: Parameter 6-15 Terminal 53 High Ref./Feedb. Value
6-15 Terminal 53 High Ref./Feedb. Value
Default value: Size related Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the analog input scaling value that corresponds to the maximum reference feedback value set in
parameter 6-11 Terminal 53
High Voltage
and
parameter 6-13 Terminal 53 High Current
.
Parameter 6-16 Terminal 53 Filter Time Constant
Table 351: Parameter 6-16 Terminal 53 Filter Time Constant
6-16 Terminal 53 Filter Time Constant
Default value: 0.001 s
Parameter type: Range, 0.001 - 10 s
Setup: All setups
Conversion index: -3
Data type: Uint16
Change during operation: True
N O T I C E
This parameter cannot be adjusted while the motor is running.
Enter the filter time constant. This constant is a first-order digital low-pass filter time for suppressing electrical noise in terminal 53. A
high value improves dampening but also increases the delay through the filter.
4.7.3 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog input 2 (terminal 54).
Parameter 6-20 Terminal 54 Low Voltage
Table 352: Parameter 6-20 Terminal 54 Low Voltage
6-20 Terminal 54 Low Voltage
Default value: Size related
Parameter type: Range, -10.00 - par. 6-21 V
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Enter the low voltage value. This analog input scaling value should correspond to the minimum reference value set in
parameter
3-02 Minimum Reference
.
AU373327181955en-000101 / 130R1208
182 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide