Parameter 5-57 Term. 33 Low Ref./Feedb. Value
Table 324: Parameter 5-57 Term. 33 Low Ref./Feedb. Value
5-57 Term. 33 Low Ref./Feedb. Value
Default value: Size related Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the low reference value [RPM] for the motor shaft speed. This is also the low feedback value, see also
parameter 5-52 Term. 29
Low Ref./Feedb. Value
.
Parameter 5-58 Term. 33 High Ref./Feedb. Value
Table 325: Parameter 5-58 Term. 33 High Ref./Feedb. Value
5-58 Term. 33 High Ref./Feedb. Value
Default value: Size related Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the high reference value [RPM] for the motor shaft speed. See also
parameter 5-53 Term. 29 High Ref./Feedb. Value
.
Parameter 5-59 Pulse Filter Time Constant #33
Table 326: Parameter 5-59 Pulse Filter Time Constant #33
5-59 Pulse Filter Time Constant #33
Default value: 100 ms
Parameter type: Range, 1 - 1000 ms
Setup: All setups
Conversion index: -3
Data type: Uint16
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
Enter the pulse filter time constant. The low-pass filter reduces the influence and dampens oscillations on the feedback signal from
the control. This is an advantage if there is a lot of noise in the system.
4.6.6 5-6* Pulse Outputs
N O T I C E
These parameters cannot be adjusted while the motor is running.
These parameters configure pulse outputs with their functions and scaling. Terminals 27 and 29 are allocated to pulse output via
parameter 5-01 Terminal 27 Mode
and
parameter 5-02 Terminal 29 Mode
, respectively.