14-20 Reset Mode
Option:
Function:
[2]
Automatic reset
x 2
[3]
Automatic reset
x 3
[4]
Automatic reset
x 4
[5]
Automatic reset
x 5
[6]
Automatic reset
x 6
[7]
Automatic reset
x 7
[8]
Automatic reset
x 8
[9]
Automatic reset
x 9
[10] Automatic reset
x 10
[11] Automatic reset
x 15
[12] Automatic reset
x 20
[13] Infinite auto
reset
Select
[13] Infinite Automatic Reset
for
continuous resetting after tripping.
[14] Reset at power-
up
14-21 Automatic Restart Time
Range:
Function:
10 s
*
[0 - 600
s]
Enter the time interval from trip to start of the
automatic reset function. This parameter is
active when
is set
to
[1] - [13] Automatic reset
.
14-22 Operation Mode
Option:
Function:
Specify normal operation, perform tests, or
initialise all parameters except for
,
, and
. This function is
only active when the power is cycled to the
frequency converter.
[0]
*
Normal
operation
Normal operation with motor selected.
[2]
Initiali-
sation
Reset all parameter values to default settings,
except for
, and
. The frequency
converter resets during the next power-up.
14-24 Trip Delay at Current Limit
Range:
Function:
60 s
*
[0 -
60 s]
Enter the current limit trip delay in seconds. When
the output current reaches the current limit
(
), a warning is
triggered. When the current limit warning has
been continuously present for the period specified
in this parameter, the frequency converter trips. To
run continuously in current limit without tripping,
set the parameter to 60 s=Off. Thermal monitoring
of the frequency converter remains active.
14-25 Trip Delay at Torque Limit
Range:
Function:
60 s
*
[0 -
60 s]
Enter the torque limit trip delay in seconds. When
the output torque reaches the torque limits
(
parameter 4-16 Torque Limit Motor Mode
and
parameter 4-17 Torque Limit Generator Mode
), a
warning is triggered. When the torque limit
warning has been continuously present for the
period specified in this parameter, the frequency
converter trips. Disable the trip delay by setting
the parameter to 60 s=Off. Thermal monitoring of
the frequency converter remains active.
14-27 Action At Inverter Fault
Option:
Function:
Select how the frequency converter reacts when
an overvoltage or grounding fault occurs.
[0]
Trip
Disables the protection filters and trips at the first
fault.
[1]
*
Warning Runs the protection filters normally.
14-28 Production Settings
Option:
Function:
[0]
*
No action
[1]
Service reset
[3]
Software Reset
14-29 Service Code
Range:
Function:
0
*
[0 - 0x7FFFFFFF ]
For internal use only.
4.13.4 14-3* Current Limit Control
The frequency converter features an integral current limit
controller, which is activated when the motor current, and
thus the torque, is higher than the torque limits set in
parameter 4-16 Torque Limit Motor Mode
and
parameter 4-17 Torque Limit Generator Mode
.
When the current limit is reached during motor operation
or regenerative operation, the frequency converter tries to
reduce torque below the preset torque limits as quickly as
possible without losing control of the motor.
Parameter Descriptions
Programming Guide
MG06C602