4.15 Parameters: 16-** Data Readouts
4.15.1 16-0* General Status
16-00 Control Word
Range:
Function:
0
*
[0 - 65535 ] View the control word sent from the frequency
converter via the serial communication port in
hex code.
16-01 Reference [Unit]
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-4999 - 4999
ReferenceFeed-
backUnit]
View the present reference
value applied on impulse
or analog basis in the unit
resulting from the configu-
ration selected in
parameter 1-00 Configu-
ration Mode
16-02 Reference [%]
Range:
Function:
0 %
*
[-200 -
200 %]
View the total reference. The total reference
is the sum of digital, analog, preset, bus,
and freeze references, plus catch up and
slow down.
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ] View the status word sent from the frequency
converter via the serial communication port in
hex code.
16-05 Main Actual Value [%]
Range:
Function:
0 %
*
[-200 - 200 %] View the 2-byte word sent with the status
word to the bus master reporting the
main actual value.
16-09 Custom Readout
Range:
Function:
0 CustomRea-
doutUnit
*
[0 - 9999
CustomRea-
doutUnit]
View the custom readout from
parameter 0-30 Custom
Readout Unit
to
parameter 0-32 Custom
Readout Max Value
4.15.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
*
[0 -
1000
kW]
Displays motor power in kW. The calculated
value shown is based on the actual motor
voltage and motor current. The value is filtered,
and therefore approximately 30 ms may pass
from when an input value changes to when
the data readout values change. The resolution
of readout value on fieldbus is in 10 W steps.
16-11 Power [hp]
Range:
Function:
0 hp
*
[0 -
1000 hp]
View the motor power in HP. The value shown
is calculated on the basis of the actual motor
voltage and motor current. The value is
filtered, and therefore approximately 30 ms
may pass from when an input value changes
to when the data readout values change.
16-12 Motor Voltage
Range:
Function:
0 V
*
[0 - 65535 V] View the motor voltage, a calculated value
is used for controlling the motor.
16-13 Frequency
Range:
Function:
0 Hz
*
[0 - 6553.5 Hz] View the motor frequency, without
resonance dampening.
16-14 Motor current
Range:
Function:
0 A
*
[0 - 655.35
A]
View the motor current measured as an
average value, I
RMS
. The value is filtered, and
approximately 30 ms may pass from when
an input value changes to when the data
readout values change.
16-15 Frequency [%]
Range:
Function:
0 %
*
[0 -
6553.5 %]
View a 2-byte word reporting the actual
motor frequency (without resonance
dampening) as a percentage (scale
0000-4000 hex) of
parameter 4-19 Max
Output Frequency
.
16-16 Torque [Nm]
Range:
Function:
0 Nm [-30000 -
30000 Nm]
View the torque value with sign, applied to
the motor shaft. Some motors supply more
than 160% torque. As a result, the minimum
value and the maximum value depend on
Parameter Descriptions
VLT
®
AutomationDrive FC 360
102
Danfoss A/S © 7/2015 All rights reserved.
MG06C602
4
4