21-13 Ext. 1 Reference Source
Option:
Function:
This parameter defines which input
on the frequency converter should be
treated as the source of the reference
signal for the closed-loop 1 controller.
Analog input X30/11 and analog
input X30/12 refer to inputs on the
VLT
®
General Purpose I/O Card MCB
101.
[0]
*
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
[29] Analog Input X48/2
[30] Ext. Closed Loop 1
[31] Ext. Closed Loop 2
[32] Ext. Closed Loop 3
[33] PCD Bus Reference
[35] Digital input select
21-14 Ext. 1 Feedback Source
Option:
Function:
This parameter defines which input
on the frequency converter should
be treated as the source of the
feedback signal for the closed-loop 1
controller. Analog input X30/11 and
analog input X30/12 refer to inputs
on the VLT
®
General Purpose I/O
Card MCB 101.
[0]
*
No function
[1]
Analog Input 53
[2]
Analog Input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog Input X30/11
[8]
Analog Input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[15]
Analog Input X48/2
[99]
Normal Feedback
[100] Bus Feedback 1
[101] Bus Feedback 2
[102] Bus feedback 3
[104] Sensorless Flow
21-14 Ext. 1 Feedback Source
Option:
Function:
[105] Sensorless Pressure
[200] Ext. Closed Loop 1
[201] Ext. Closed Loop 2
[202] Ext. Closed Loop 3
21-15 Ext. 1 Setpoint
Range:
Function:
0
ExtPID1Unit
*
[-999999.999 -
999999.999
ExtPID1Unit]
The setpoint reference is used in
extended 1 closed loop. Ext.1
Setpoint is added to the value
from the Ext.1 Reference Source
selected in
.
21-17 Ext. 1 Reference [Unit]
Range:
Function:
0 ExtPID1Unit
*
[-999999.999 -
999999.999
ExtPID1Unit]
Readout of the reference
value for the closed-loop
1 controller.
21-18 Ext. 1 Feedback [Unit]
Range:
Function:
0 ExtPID1Unit
*
[-999999.999 -
999999.999
ExtPID1Unit]
Readout of the feedback
value for the closed-loop
1 controller.
21-19 Ext. 1 Output [%]
Range:
Function:
0 %
*
[0 - 100 %] Readout of the output value for the closed-
loop 1 controller.
3.18.3 21-2* Closed Loop 1 PID
21-20 Ext. 1 Normal/Inverse Control
Option:
Function:
[0]
*
Normal Reduces the output when feedback is higher than
the reference.
[1]
Inverse Increase the output when feedback is higher than
the reference.
21-21 Ext. 1 Proportional Gain
Range:
Function:
0.50
*
[0 - 10 ] The proportional gain contains the factor
indicating the number of times the error
between the setpoint and the feedback signal is
to be applied.
If the product error times gain jumps with a value equal to
what is set in
parameter 3-03 Maximum Reference
, the PID
controller tries to change the output speed equal to what
is set in
parameter 4-13 Motor Speed High Limit [RPM]
/
Parameter Description
VLT
®
AQUA Drive FC 202
172