Table 49: Fuse Options
Input voltage (V)
Model
Bussmann part number
380–480
N355–N400
170M6014
380–480
N450–N560
170M7309
525–690
All
170M7342
are suitable for use on a circuit capable of delivering 100000 A
rms
(symmetrical), depending on the drive
voltage rating. With the proper fusing, the drive short-circuit current rating (SCCR) is 100000 A
rms
. E1h and E2h drives are supplied with
internal drive fusing to meet the 100 kA SCCR. E3h and E4h drives must be fitted with Type aR fuses to meet the 100 kA SCCR.
NOTICE
DISCONNECT SWITCH SCCR REQUIREMENTS
All units ordered and supplied with a factory-installed disconnect switch require Class L branch circuit fusing to meet the 100
kA SCCR for the drive.
-
If a circuit breaker is used, the SCCR rating is 42 kA. The input voltage and power rating of the drive determines the specific
Class L fuse. The input voltage and power rating are found on the product nameplate.
Table 50: Disconnect Switch SCCR Requirements
Input voltage (V)
Model
Short circuit rating (A)
Required protection
380–480
N355–N450
42000
Circuit breaker
100000
Class L fuse, 800 A
380–480
N500–N560
42000
Circuit breaker
100000
Class L fuse, 1200 A
525–690
N450–N630
42000
Circuit breaker
100000
Class L fuse, 800 A
525–690
N710–N800
42000
Circuit breaker
100000
Class L fuse, 1200 A
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
142 | Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...