Manual initialization procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialization does not reset the following
adjustable frequency drive information:
•
15-00 Operating hours
•
15-03 Power-ups
•
15-04 Over Temps
•
15-05 Over Volts
5.4 Basic Programming
5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basic
motor and application parameters.
•
At first power-up or after initialization of the
adjustable frequency drive, SmartStart starts by
itself.
•
Follow on-screen instructions to complete
commissioning of the adjustable frequency drive.
Always reactivate SmartStart by selecting
Quick
Menu Q4 - SmartStart
.
•
For commissioning without use of the SmartStart
wizard, refer to
chapter 5.4.2 Commissioning via
or the
Programming Guide
.
NOTICE!
Motor data are required for the SmartStart set-up. The
required data are normally available on the motor
nameplate.
The SmartStart configures the adjustable frequency drive in
three phases, each consisting of several steps, see
Phase
Comment
1
Basic Programming
Program, e.g., motor data
2
Application Section
Select and program
appropriate application:
•
Single pump/motor
•
Motor alternation
•
Basic cascade control
•
Master/follower
3
Water and Pump Features
Go to water and pump
dedicated parameters
Table 5.6 SmartStart, Set-up in three Phases
5.4.2 Commissioning via [Main Menu]
Recommended parameter settings are intended for start-
up and checkout purposes. Application settings may vary.
Enter data with power ON, but before operating the
adjustable frequency drive.
1.
Press [Main Menu] on the LCP.
2.
Press the navigation keys to scroll to parameter
group
0-** Operation/Display
and press [OK].
130BP066.10
1107 RPM
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.84 A
1 (1)
Main Menu
Figure 5.2 Main Menu
Commissioning
VLT
®
AQUA Drive FC 202
28