1) For type of fuse see
2) American wire gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerence relates to
variety in voltage and cable conditions). Values are based on a typical motor efficiency (eff2/eff3 border line).
Motors with lower efficiency also add to the power loss in the frequency converter and opposite. If the switching
frequency is increased compared to the default setting, the power losses may rise significantly. LCP and typical
control card power consumptions are included. Further options and customer load may add up to 30 W to the
losses (though typical only 4 W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state-of-the-art equipment, some measurement inaccuracy must be
allowed for (+/-5%).
8.1.2 Derating for Temperature
The frequency converter automatically derates the
switching frequency, switching type, or output current
under certain load or ambient conditions as described in
the following.
,
,
, and
show the derating curve for SFAWM and 60 AVM
switching modes.
130BX474.10
70
80
90
1
60
100
110
2
3
4
5
6
7
8
9
0
50
o
50 C
o
55 C
o
45 C
Iout [%]
fsw [kHz]
Figure 8.1 Derating Enclosure Size D, N160 to N250 380–480 V
(T5) Normal Overload 110%, 60 AVM
130BX476.10
Iout [%]
fsw [kHz]
o
70
80
90
60
100
110
2
4
6
50 C
o
55 C
0
o
45 C
50
o
40 C
1
3
5
Figure 8.2 Derating Enclosure Size D, N160 to N250 380–480 V
(T5) Normal Overload 110%, SFAVM
130BX478.10
Iout [%]
fsw [kHz]
o
70
80
90
1
60
100
110
2
3
4
5
6
7
50 C
o
55 C
0
50
o
45 C
Figure 8.3 Derating Enclosure Sizes E and F, P315 to P710
380–480 V (T5) Normal Overload 110%, 60 AVM
130BX480.10
Iout [%]
fsw [kHz]
o
70
80
90
1
60
100
110
2
3
4
5
50 C
55 C
0
o
45 C
o
50
o
40 C
Figure 8.4 Derating Enclosure Sizes E and F, P315 to P710
380–480 V (T5) Normal Overload 110%, SFAVM
Specifications
Installation Manual
MG21B322
Danfoss A/S © 10/2015 All rights reserved.
85
8
8