The frequency points are defined in par.1-56
This parameter is an array parameter [0-5] and is only accessible when par. 1-01
Motor Control
Principle
is set to
U/f
[0].
1-56 U/f Characteristic - F
Range:
Function:
0 Hz*
[0 - 1000.0 Hz]
Enter the frequency points to manually form a U/f-characteristic matching the motor.
The voltage at each point is defined in par.1-55
.
This parameter is an array parameter [0-5] and is only accessible when par. 1-01
Motor Control
Principle
is set to
U/f
[0].
2.3.6 1-6* Load Depend. Setting
Parameters for adjusting the load-dependent motor settings.
1-60 Low Speed Load Compensation
Range:
Function:
100 %*
[0 - 300 %]
Enter the % value to compensate voltage in relation to load when the motor is running at low speed
and obtain the optimum U/f characteristic. The motor size determines the frequency range within
which this parameter is active.
Motor size
Change over
0.25 kW - 7.5 kW
< 10 Hz
11 kW - 45 kW
< 5 Hz
55 kW - 550 kW
< 3-4 Hz
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
41
2