6.4 Parameters: 5-** Digital In/Out
Parameters for configuring the I/O mode. NPN/PNP and
setting up I/O to Input or Output.
5-00 Digital I/O Mode
Option:
Function:
Digital inputs and programmed digital outputs are
pre-programmable for operation either in PNP or NPN
systems.
[0]
*
PNP No reaction to signals transmitted to the terminal.
[1]
NPN Resets the frequency converter after a TRIP/ALARM.
Not all alarms can be reset.
NOTICE
When changing this parameter, a power cycle must be
carried out before the parameter change is active.
This parameter cannot be adjusted while the AFE is
running.
5-01 Terminal 27 Mode
Option:
Function:
[0]
Input
Defines terminal 27 as a digital input.
[1]
*
Output
Defines terminal 27 as a digital output.
This parameter cannot be adjusted while the AFE is
running.
5-02 Terminal 29 Mode
Option:
Function:
[0]
Input
Defines terminal 29 as a digital input.
[1]
*
Output
Defines terminal 29 as a digital output.
This parameter cannot be adjusted while the AFE is
running.
6.4.1 5-1* Digital Inputs
Parameters for configuring the input functions for the
input terminals.
NOTICE
For the parameters in group
5-1* Digital Inputs
it is
possible to choose between the different possible
functions related to the input on this terminal.
[0] No
operation
No reaction to signals transmitted to the
terminal.
[1] Reset
Resets AFE after a TRIP/ALARM. Not all alarms
can be reset.
[8] Start
(Default Digital input 18): Select start for a
start/stop command. Logic ‘1’ = start, logic ‘0’ =
stop.
5-10 Terminal 18 Digital Input
Option:
Function:
[0]
No operation
[1]
Reset
[8]
*
Start
[23]
*
Set-up select bit
0
Select Set-up select bit 0 or Select Set-
up select bit 1 to select one of the four
set-ups. Set
to Multi Set-up.
[24]
*
Set-up select bit
1
(Default Digital input 32): Same as Set-
up select bit 0 [23].
5-11 Terminal 19 Digital Input
Option:
Function:
[0]
No operation
[1]
*
Reset
[8]
Start
[23]
*
Set-up select bit
0
Select Set-up select bit 0 or Select Set-
up select bit 1 to select one of the four
set-ups. Set
to Multi Set-up.
[24]
*
Set-up select bit
1
(Default Digital input 32): Same as Set-
up select bit 0 [23].
5-12 Terminal 27 Digital Input
Option:
Function:
[0]
*
No operation
[1]
Reset
[8]
Start
[23]
*
Set-up select bit
0
Select Set-up select bit 0 or Select Set-
up select bit 1 to select one of the four
set-ups. Set
to Multi Set-up.
[24]
*
Set-up select bit
1
(Default Digital input 32): Same as Set-
up select bit 0 [23].
5-13 Terminal 29 Digital Input
Option:
Function:
[0]
*
No operation
[1]
Reset
[8]
Start
[23]
*
Set-up select bit
0
Select Set-up select bit 0 or Select Set-
up select bit 1 to select one of the four
set-ups. Set
to Multi Set-up.
[24]
*
Set-up select bit
1
(Default Digital input 32): Same as Set-
up select bit 0 [23].