4.2.4 Lifting
Always lift the unit in the dedicated lifting eyes. Use a bar
to avoid bending the lifting holes.
130BB494.10
Figure 4.2 Recommended Lifting Method for AAF 005, Frame
Sizes D9 and E7.
130BB642.10
Figure 4.3 Recommended Lifting Method for AAF 006, Frame
Sizes D13 and E9.
NOTE!
The lifting bar must be able to handle the weight of the unit. See
Mechanical Dimensions
for the weight of the different
frame sizes. Maximum diameter for bar is 1 in [25mm]. The angle from the top of the unit to the lifting cable should be 60
°
or greater.
How to Install
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
4-3
4