VLT
®
4000 VT
Programming
■
Programming
Using the [EXTEND MENU] key, it
is possible to have access to all the
parameters for the AFD.
■
Operation and Display 001 - 017
This parameter group allows to set up parameters
such as language, display readout and the possibility of
making the function keys on the control unit inactive.
001 Language
(LANGUAGE)
Value:
✭
English (ENGLISH)
[0]
German (DEUTSCH)
[1]
French (FRANCAIS)
[2]
Danish (DANSK)
[3]
Spanish (ESPAÑOL)
[4]
Italian (ITALIANO)
[5]
Swedish (SVENSKA)
[6]
Dutch (NEDERLANDS)
[7]
Portuguese (PORTUGUESA)
[8]
State when delivered may vary from factory setting.
Function:
The choice in this parameter defines the language
to be used on the display.
Description of choice:
There is a choice of the languages indicated.
■
The Setup configuration
VLT 4000 VT has four Setups (parameter Setups) that
can be programmed independently of each other. The
active Setup can be selected in parameter 002
Active
Setup
. The active Setup number will be shown in the
display under "Setup". It is also possible to set the
VLT AFD to Multi-Setup to allow switching of Setups
with the digital inputs or serial communication.
Setup shifts can be used in systems where, one Setup
is used during the day and another at night.
Parameter 003
Copying of Setups
enables copying
from one Setup to another.
By means of parameter 004
LCP copy
, all Setups
can be transferred from one VLT AFD to another by
moving the control panel. First all parameter values are
copied to the control panel. This can then be moved
to another VLT AFD, where all parameter values can
be copied from the control unit to the VLT AFD.
002 Active Setup
(ACTIVE SETUP)
Value:
Factory Setup (FACTORY SETUP)
[0]
✭
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Setup 3 (SETUP 3)
[3]
Setup 4 (SETUP 4)
[4]
MultiSetup (MULTI SETUP)
[5]
Function:
The choice in this parameter defines the Setup number
you want to control the functions of the AFD. All
parameters can be programmed in four individual
parameter Setups, Setup 1 - Setup 4.
In addition, a pre-programmed Setup called the
Factory Setup exists. This only allows specific
parameters to be changed.
Description of choice:
Factory Setup
[0] contains the parameter values pre-set
at the factory. Can be used as a data source if the
other Setups are to be returned to a common state. In
this case Factory Setup is selected as the active Setup.
Setups 1-4
[1]-[4] are four individual Setups that
can be selected as required.
MultiSetup
[5] is used if remote switching between
different Setups is required. Terminals 16/17/29/32/33
and the serial communication port can be used
for switching between Setups.
MG.40.A7.22 - VLT is a registered Danfoss trademark