General warning

The voltage of the adjustable frequency

drive is dangerous whenever the drive

is connected to the AC line. Incorrect

installation of the motor or drive may cause damage

to the equipment, serious injury or death. Comply

with the safety instructions in this manual as well as

local and national rules and safety regulations.

These rules concern your safety:

1. Disconnect the adjustable frequency drive from

the AC line if repair work is to be carried out. Wait

4 minutes to allow for electrical discharge before

removing motor and AC line connectors.

2. The [STOP/RESET] key on the control panel

of the adjustable frequency drive does not

disconnect the equipment from the AC line.

Do not use it as a safety switch.

3. The unit must be grounded correctly. The user

must be protected against supply voltage and the

motor protected against overload in accordance

with applicable national and local regulations.

4. The ground leakage currents are higher than 3.5 mA.

5. Protection against motor overload is not included in

the factory setting. If this function is required, set

parameter 128

Motor thermal protection

to

ETR

trip

or

ETR warning

. For North America: The ETR

functions provide class 20 overload protection for

the motor, in accordance with NEC requirements.

6. Do not remove the terminal plugs for the motor

and AC line supply while the adjustable frequency

drive is connected to the AC line. Ensure that

the AC line supply has been disconnected and

that 4 minutes has passed before removing

motor and AC line plugs.

7. The DC bus terminals are another high voltage

input that must be disconnected before servicing

the drive. Ensure that all voltage inputs have

been disconnected and that 4 minutes has

passed before repair work begins.

Warnings against unintended start:

1. The motor can be started by means of digital

commands, bus commands, references or

a local start command whenever the drive

is connected to the AC line. Therefore, an

unintended start may occur anytime power is

applied. Never service the drive or equipment

when power is applied to the drive.

2. The motor may start while parameters are

being changed. Always activate the stop key

[STOP/RESET] by pressing it before data is modified.

3. A motor that has been stopped may start if

faults occur in the electronics of the drive, or

if a temporary overload or fault clears in the

AC line or motor connection.

Motor overload protection

The electronic thermal relay (ETR) in UL listed

VLTs provides Class 20 motor overload protection

in accordance with the NEC in single motor

applications when parameter 128 is set for "ETR

TRIP" and parameter 105

Motor current

is set

for the rated motor current.

195NA139.10

Warning:

It can be extremely dangerous to touch the electrical parts
even when the mains supply has been disconnected.
Also ensure that other voltage inputs are disconnected
from load sharing through the DC bus.
Wait at least 4 minutes after the input power has been
removed before servicing the drive.