Control valve sizing diagram 

for steam

(continued)

1  For saturated steam

Design data:

Flow rate: 1000 kg/h

Absolute inlet pressure: 5 bar (500 kPa)

- follow dashed line -

The absolute inlet pressure is 500 kPa. 40% of 

this is 200 kPa.

Locate the diagonal line corresponding to the 

pressure drop of 200 kPa (line A-A).

Read the absolute inlet pressure on the lower left 

hand scale (point B), and draw a horizontal line 

across until it meets the pressure drop diagonal 

(A-A) at point C. 

From this point extend a vertical line upwards 

until it meets the horizontal line representing 

the steam flow of 1000 kg/h from point D. The 

intersection of this is point E. 

The nearest diagonal kvs line above this is line 

F-F with a k

vs

 of 25 (point E’). If the ideal valve size 

is not available the next largest size should be 

selected to ensure design flow.

The pressure drop through valve at the flow rate 

is found by the intersection of the 1000 kg/h 

line with F-F (point E’) and dropping a vertical; 

this actually hits the horizontal line for 500 kPa 

(point E’’) inlet pressure at a pressure drop 

diagonal of 70 kPa. This is only 14 % of the inlet 

pressure and the control quality will not be 

good until the valve has partially closed. As with 

all steam valves this compromise is necessary 

since the next smaller valve would not pass the 

required flow (maximum flow would have been 

about 600 kg/h).

The maximum flow for same inlet pressure 

is found by extending the vertical line (C-E) 

through point E until it crosses the k

VS

 25 line F-F 

(point E’’’) and reading off the flow (1700 kg/h).

2  For superheated steam

Design data:

Flow rate: 500 kg/h

Absolute inlet pressure: 5 bar (500 kPa)

Steam temperature: 190 °C

The procedure for superheated steam is much 

the same as for saturated steam, but uses a 

different flow scale which slightly elevates the 

readings according to the degree of superheat. 

- follow dotted line -

As before, the diagonal pressure drop line 

A-A is located as before for 40 % of 500  

(200 kg/h). The horizontal inlet pressure line 

through point B is now extended to the left to 

read off the corresponding saturated steam 

temperature at point G (150 °C). The difference 

between the saturated steam temperature and 

the superheated steam temperature is  

190 °C - 150 °C = 40 °C. 

The superheated steam flow is found on the 

upper right hand scale, point H, and the diagonal 

line is followed down from here until it meets 

a vertical line from the steam temperature 

elevation (40 °C) at point J.

As before, the horizontal line through point B is 

drawn to cut line A-A at point C and the point 

where the vertical line from this point meets the 

horizontal line from point J is the operating point 

(point K). This horizontal line, J-K, is the corrected 

flow line. The nearest diagonal line above this is 

for k

vs

 10 (point K’). A vertical line dropped from 

the intersection of J-K with the 10 k

vs

 line intersects 

the 500 kPa inlet pressure line (point K’’) at a 

pressure drop diagonal of about 150 kPa. This 

is about 30% of the inlet pressure which will 

give reasonable control quality (compared to 

recommended ratio of 40%). 

Summary of Contents for VFS 2

Page 1: ...15 50 065Z7020 Stem heater 24 V AC DC AMV E 85 86 and and VFS 2 valves DN 65 100 065Z7021 Stem heater 24 V AC DC AMV E 55 56 655 658 659 and VFS 2 valves DN 65 100 065Z7022 Adapter AMV E 25 SU SD AMV...

Page 2: ...If max closing pressure is smaller than 4 bar than the recommended p is the same as closing p 3 Values in parentheses are based on the force of the actuator AMV E 25 SU SD only Technical data Nominal...

Page 3: ...antled and the elements sorted into various material groups before disposal Tmax 150 C for AMV E 25 SU SD 35 Tmax 200 C for other AMV E Tmax 150 C 200 C AMV E 25 SU SD 35 Leave sufficient clearance to...

Page 4: ...hence The largest valve with kVS 10 would give a pressure drop of 36 kPa point D 395 0 55 36 36 authority valve hence Generally the smaller valve would be selected resulting in a valve authority highe...

Page 5: ...mediately upstream of the valve being dropped across the valve when fully open At this condition the steam is travelling at or close to its critical velocity approx 300 m s and throttling will occur o...

Page 6: ...re is found by extending the vertical line C E through point E until it crosses the kVS 25 line F F point E and reading off the flow 1700 kg h 2 For superheated steam Design data Flow rate 500 kg h Ab...

Page 7: ...5 290 484 525 568 145 18 8 23 0 80 310 503 544 587 160 18 8 28 1 100 350 530 571 614 190 22 8 40 7 DN L H H1 k d n number Valve weight kg mm 15 130 237 383 65 14 4 3 6 20 150 237 383 75 14 4 4 3 25 16...

Page 8: ...the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed All t...

Reviews: