For more information, refer to the standard IEC61800-2.
12.7.2 Power Ratings for Mains Voltage 208–240 V
Table 50: Power Ratings in Mains 208–240 V, 50 Hz, 3~
Enclo-
sure size
Drive
type
Input
current
I
in
(1)
Low load-
ability: I
L
[A]
(2)
Low load-
ability:
10% over-
load I [A]
High
loadabili-
ty: I
H
[A]
(2)
High load-
ability:
50% over-
load I [A]
Loadabili-
ty: Max I
S
2 s
Motor
shaft pow-
er
(3)
: 10%
overload
40°C [kW]
Motor
shaft pow-
er
(3)
: 50%
overload
50°C [kW]
FR4
0003
3.7
3.7
4.1
2.4
3.6
4.8
0.55
0.37
0004
4.8
4.8
5.3
3.7
5.6
7.4
0.75
0.55
0007
6.6
6.6
7.3
4.8
7.2
9.6
1.1
0.75
0008
7.8
7.8
8.6
6.6
9.9
13.2
1.5
1.1
0011
11
11.0
12.1
7.8
11.7
15.6
2.2
1.5
0012
12.5
12.5
13.8
11.0
16.5
22.0
3.0
2.2
FR5
0017
17.5
17.5
19.3
12.5
18.8
25.0
4.0
3.0
0025
25
25
27.5
17.5
26.3
35.0
5.5
4.0
0031
31
31
34.1
25.0
37.5
50.0
7.5
5.5
FR6
0048
48
48
52.8
31.0
46.5
62.0
11.0
7.5
0061
61
61.0
67.1
48.0
72.0
96.0
15.0
11.0
FR7
0075
75
75.0
83.0
61.0
92.0
122.0
22.0
15.0
0088
88
88.0
97.0
75.0
113.0
150.0
22.0
22.0
0114
114
114.0
125.0
88.0
132.0
176.0
30.0
22.0
FR8
0140
140
140.0
154.0
105.0
158.0
210.0
37.0
30.0
0170
170
170.0
187.0
140.0
210.0
280.0
45.0
37.0
0205
205
205.0
226.0
170.0
255.0
340.0
55.0
45.0
FR9
0261
261
261.0
287.0
205.0
308.0
410.0
75.0
55.0
0300
300
300.0
330.0
245.0
368.0
490.0
90.0
75.0
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
See
3
230 V
AQ275638903263en-000601 / DPD00910
156 | Danfoss A/S © 2022.12