Table 38: Dimensions of the Mounting Holes in mm (inch) for VACON
®
NXS/NXP AC Drive, FR11 Standalone
Drive type
E1Ø, grommet in-
side diameter
(1)
E1Ø, gland
plate hole
E2Ø, grommet in-
side diameter
(1)
E2Ø, gland
plate hole
E3Ø, mounting holes
for fixing to floor
0590 5–0730 5
0460 6–0590 6
4 x 21
(4 x 0.83)
4 x 28
(4 x 1.10)
8 x 48
(8 x 1.89)
8 x 60
(8 x 2.36)
9 x 11
(9 x 0.43)
1
Same as maximum cable thickness. NOTE! Cable clamps have 40 mm internal diameter. The clamps are used for 360 degree grounding of the
shield. Exposing the cable shield decreases outer diameter of the cable so the recommended 3x185+95 mm
2
MCCMK motor cables fit in the clamp.
12.3 Cable and Fuse Sizes
12.3.1 List of Cable and Fuse Size Information
This topic lists the links to find the cable and fuse size tables for VACON
™
NXS and NXP Air Cooled AC Drive.
Use external gG/gL or T/J fuses for overload and short-circuit protection.
12.3.2 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9
12.3.4 Cable and Fuse Sizes for 525–690 V, FR6 to FR9
12.3.6 Cable and Fuse Sizes for 380–500 V, FR10 to FR11 Standalone
12.3.8 Cable and Fuse Sizes for 525–690 V, FR10 to FR11
For AC Drives in North America, see:
12.3.3 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9, North America
12.3.5 Cable and Fuse Sizes for 525–690 V (UL Rating 600 V), FR6 to FR9, North America
12.3.7 Cable and Fuse Sizes for 380–500 V, FR10 to FR11, North America
12.3.9 Cable and Fuse Sizes for 525–690 V (UL Rating 600 V), FR10 to FR11, North America
12.3.2 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9
Table 39: Cable and Fuse Sizes for VACON
®
NXS/NXP
Enclosure
size
Drive type
I
L
[A]
Fuse
(gG/gL) [A]
Mains, motor and
brake resistor cable
Cu
(1)
[mm
2
]
Mains terminal [mm
2
] Grounding terminal
[mm
2
]
FR4
0003 2–0008 2
0003 5–0009 5
3–8
3–9
10
3*1.5+1.5
1–4
1–4
0011 2–0012 2
0012 5
11–12
12
16
3*2.5+2.5
1–4
1–4
FR5
0017 2
0016 5
17
16
20
3*4+4
1–10
1–10
0025 2
0022 5
25
22
25
3*6+6
1–10
1–10
0031 2
0031 5
31
31
35
3*10+10
1–10
1–10
FR6
0048 2
0038 5–0045 5
48
38–45
50
3*10+10
2.5–50 Cu
6–50 Al
2.5–35
0061 2
61
63
3*16+16
2.5–50 Cu
2.5–35
AQ275638903263en-000601 / DPD00910