![Danfoss Vacon NXP Design Manual Download Page 20](http://html1.mh-extra.com/html/danfoss/vacon-nxp/vacon-nxp_design-manual_3535777020.webp)
Table 12: Technical Data for Liquid-cooled DC Filters
Code Num-
ber
Filter type code
Manufacturer
part code
Rated
voltage
[V DC]
Cooling Nominal
current at
liquid tem-
perature
45 °C [A]
Power
loss at liq-
uid tem-
perature
45 °C [W]
Protec-
tion
rating
Switching
frequency
[kHz]
181B5968
LDC-0160-6-0-CPt 41787-SET-
PT100
1025
Liquid
160
600
IP00
5
181B5969
LDC-0160-6-0-CTr 41787-SET-
THERMIK
181B5974
LDC-0340-6-0-CPt 36858-SET-
PT100
1025
Liquid
340
1100
IP00
5
181B5975
LDC-0340-6-0-CTr 36858-SET-
THERMIK
181B5984
LDC-0700-6-0-CPt 38175-SET-
PT100
1025
Liquid
700
2200
IP00
5
181B5985
LDC-0700-6-0-CTr 38175-SET-
THERMIK
181B5988
LDC-1150-6-0-CPt 36859-SET-
PT100
1025
Liquid
1134
2700
IP00
5
181B5989
LDC-1150-6-0-CTr 36859-SET-
THERMIK
7.5 Dimensions
. Details of the terminal connec-
tions can be found in the mechanical drawing of the specific filter.
Table 13: Dimensions of the 1-phase Inductors
Filter type code
Drawing
Dimensions
Weight [kg]
A
B
C
D
E
F
G
H
LDC-0010-6-0-APt
154±2
116
271±5
100
100
69
7x14
–
8
LDC-0010-6-0-ATr
LDC-0020-5-0-APt
154±2
129
329±5
100
100
69
7x14
–
10
LDC-0020-5-0-ATr
LDC-0030-6-0-APt
158±5
141
299±3
100
100
69
7x14
–
14
LDC-0030-6-0-ATr
LDC-0050-6-0-APt
260±5
139±5
271±3
96
155
80
9
–
17
LDC-0050-6-0-ATr
LDC-0092-5-0-APt
303±10
161±5
269±5
96
185
80
9
–
20
LDC-0092-5-0-ATr
LDC-0092-6-0-APt
305±5
168±3
339±5
96
185
80
9
–
27
LDC-0092-6-0-ATr
AJ377845348678en-000101 / 172F4785
20 | Danfoss A/S © 2023.01
Specifications
DC Filters
Design Guide