The maximum load on the +24 V/EXT+24 V output per board is 150 mA. If there is a +24 V/EXT+24 V output on the board, it is locally
short circuit protected. If one of the +24 V/ EXT+24 V outputs short circuits, the others remain powered because of the local protection.
=
A
B
C
e
3
0
b
g
0
1
4
.1
0
A Maximum 150 mA
C Maximum 250 mA
B +24 V out
Illustration 17: Maximum Loads on +24 V/EXT+24 V Output
7.3.2.1 Digital Input Signal Inversions
The active signal level is different when the common inputs CMA and CMB (terminals 11 and 17) are connected to +24 V or to ground
(0 V).
The 24 V control voltage and the ground for the digital inputs and the common inputs (CMA, CMB) can be internal or external.
Control Unit
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 45
Danfoss A/S © 2019.11
Summary of Contents for VACON NXP FI10
Page 1: ...Operating Guide VACON NXI Inverters FI9 FI14...
Page 2: ......