Signal
Description
b13
Drive Ready
0=Drive is not ready
1=Drive is ready
b14
Not Used
Reserved
b15
Not Used
Reserved
10.632.2 Combination 3: Bypass - Standard
Table 128: Control Word (Standard)
Signal
Description
b0
Start/Stop
0=Stop the drive
1=Start the drive
b1
Direction
0=Clockwise
1=Counter clockwise
b2
Fault Reset
0=No Action
1=Reset active faults
b3
FB DIN 1
-
b4
FB DIN 2
-
b5
FB DIN 3
-
b6
FB DIN 4
-
b7
FB DIN 5
-
b8
No action
-
b9
No action
-
b10
No action
-
b11
No action
-
b12
No action
-
b13
No action
-
b14
No action
-
b15
Reserved
Reserved for internal use
Table 129: Status Word (Standard)
Signal
Description
b0
Ready To Switch On
0=The drive NOT ready to switch ON
1=The drive is ready to switch ON
b1
Ready To Operate
0=The drive is NOT ready to run
1=The drive is ready to run
b2
Operation Enabled
0=The drive is NOT running
AB296635287482en-000301 / DPD00903 | 323
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX