Selection number
Selection name
b6
Reserved
b7
Disables switching frequency decrease
b8
Disable the parameter "Run state parameter lock".
b9
Reserved
b10
Invert delayed digital output 1.
b11
Invert delayed digital output 2.
10.449 (ID 1085) Brake Current Limit
Location in the menu:
P2.3.4.16
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the brake current limit. The Mechanical brake closes immediately if the motor current is below the limit set
in parameter Brake Current Limit.
10.450 (ID 1087) Scaling of Generating Torque Limit
Location in the menu:
P2.2.6.6
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the analog input signal that adjusts the maximum motor generating torque.
This signal adjusts the maximum motor generating torque between 0 and maximum limit set with parameter
ID 1288
. Analog input
level zero equals zero generator torque limit.
10.451 (ID 1088) Scaling of Generating Power Limit
Location in the menu:
P2.2.6.8
(Multi-purpose Control Application)
Use this parameter to select the analog input signal that adjusts the maximum motor generating power.
This signal adjusts the maximum motor generating power between 0 and maximum limit set with parameter
ID 1290
This parame-
ter is available for Closed Loop control mode only. Analog input level zero equals zero generator power limit.
10.452 (ID 1089) Follower Stop Function
Location in the menu:
P2.11.2
(Multi-purpose Control Application)
Use this parameter to select how the follower drive stops.
Defines how the follower drive stops (when selected follower reference is not Master's ramp, parameter
ID 1081
, selection 18).
10.453 (ID 1090) Reset Encoder Counter
Location in the menu:
P2.2.7.29
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the digital input signal that resets the monitoring values Shaft Angle and Shaft Rounds to zero.
See
7.4.1 Monitoring Values (Control Panel: Menu M1)
10.454 (ID 1091) Inversion Control
Location in the menu:
P2.2.1.7
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select which input signal operation is inverted.
B00
+1
Invert external fault 1
B01
+2
Invert external fault 2
B06
+64
Invert Ambient Temperature monitor
B07
+128
Invert Input Switch
B010
+1024
Invert Klixon 1
B011
+2048
Invert Klixon 2
AB296635287482en-000301 / DPD00903
282 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...
Page 2: ......