3.4.6 Prohibit Frequency Parameters (Control Panel: Menu M2 -> G2.5)
Table 10: Prohibit Frequency Parameters, G2.5
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.5.1
Prohibit frequency range 1 low limit
0.00
320.00
Hz
0.00
509
-
P2.5.2
Prohibit frequency range 1 high limit
0.00
320.00
Hz
0.00
510
-
P2.5.3
Prohibit acc./dec. ramp
0.1
10.0
x
0.1
518
-
3.4.7 Motor Control Parameters (Control Panel: Menu M2 -> G2.6)
Table 11: Motor Control Parameters, G2.6
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.1
(1)
Motor control mode
0
1/4
-
0
600
0 = Frequency control
1 = Speed control
VACON
®
NXP:
2 = Open loop torque control
3 = Closed loop speed ctrl
4 = Closed loop torque control
P2.6.2
(1)
U/f optimisation
0
1
-
0
109
0 = Not used
1 = Automatic torque boost
P2.6.3
(1)
U/f ratio selection
0
3
-
0
108
0 = Linear
1 = Squared
2 = Programmable
3 = Linear with flux optim.
P2.6.4
(1)
Field weakening point
8.00
320.00
Hz
50.00
602
-
P2.6.5
(1)
Voltage at field weakening point
10.00
200.00
%
100.00
603
-
P2.6.6
(1)
U/f curve midpoint frequency
0.00
P2.6.4
Hz
50.00
604
-
P2.6.7
(1)
U/f curve midpoint voltage
0.00
100.00
%
100.00
605
-
P2.6.8
(1)
Output voltage at zero frequency
0.00
40.00
%
Varies
606
-
P2.6.9
Switching frequency
1.0
Varies
kHz
Varies
601
-
P2.6.10
Overvoltage controller
0
2
-
1
607
0 = Not used
1 = Used (no ramping)
2 = Used (ramping)
P2.6.11
Undervoltage controller
0
2
-
2
608
0 = Not used
1 = Used
2 = Used (ramping to zero)
P2.6.12
Load drooping
0.00
100.00
%
0.00
620
-
AB296635287482en-000301 / DPD00903
24 | Danfoss A/S © 2023.02
Standard Application
VACON® NX All-in-One
Application Guide