Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.1.9
Nominal current of the motor
0.1 x I
H
2 X I
H
A
I
H
113
-
P2.1.10
Motor cos phi
0.30
1.00
-
0.85
120
-
P2.1.11
I/O reference
0
3
-
0
117
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.12
Keypad control reference
0
3
-
2
121
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.13
Fieldbus control reference
0
3
-
3
122
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.14
Preset speed 1
0.00
P2.1.2
Hz
10.00
105
-
P2.1.15
Preset speed 2
0.00
P2.1.2
Hz
50.00
106
-
3.4.3 Input Signals (Control Panel: Menu M2 -> G2.2)
Table 7: Input Signals, G2.2
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.2.1
Start/Stop logic
0
6
-
0
300
Logic = 0
Ctrl sgn 1 = Start forward
Ctrl sgn 2 = Start reverse
Logic = 1
Ctrl sgn1 = Start/ Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/ Stop
Ctrl sgn 2 = Run enable
Logic = 3
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Stop pulse
Logic = 4
Ctrl sgn 1 = Forward pulse (edge)
Ctrl sgn 2 = Reverse pulse (edge)
Logic = 5
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Reverse pulse
Logic = 6
Ctrl sgn 1 = Start pulse (edge)
AB296635287482en-000301 / DPD00903
20 | Danfoss A/S © 2023.02
Standard Application
VACON® NX All-in-One