10.94 (ID 336) Actual Value 1 Minimum Scale
Location in the menu:
P2.2.11
(PID Control Application)
P2.2.1.11
(Pump and Fan Control Application)
Use this parameter to set the minimum scaling point of the actual value.
Sets the maximum scaling point for Actual value 2. See
.
0
100
100
140
-30
100
0
100
80
30
76.5
(15.3 mA)
17.7
(3.5 mA)
0
0
4
10.0 V
8.0
3.0
20.0 mA
20.0 mA
16.0
6.0
8.8
16.8
0
0
4
10.0 V
20.0 mA
20.0 mA
ID338 = -30%
ID339 = 140%
ID336 = 30%
ID337 = 80%
e
3
0
b
h
0
4
0
.1
0
[%]
A
[%]
A
[%]
B
[%]
B
Illustration 47: Examples of Actual Value Signal Scaling
A
Scaled input signal
B
AI
10.95 (ID 337) Actual Value 1 Maximum Scale
Location in the menu:
P2.2.12
(PID Control Application)
P2.2.1.12
(Pump and Fan Control Application)
Use this parameter to set the maximum scaling point of the actual value.
See
10.94 (ID 336) Actual Value 1 Minimum Scale
10.96 (ID 338) Actual Value 2 Minimum Scale
Location in the menu:
P2.2.13
(PID Control Application)
P2.2.1.13
(Pump and Fan Control Application)
Use this parameter to set the minimum scaling point of the actual value.
See
10.94 (ID 336) Actual Value 1 Minimum Scale
10.97 (ID 339) Actual Value 2 Maximum Scale
Location in the menu:
P2.2.14
(PID Control Application)
P2.2.1.14
(Pump and Fan Control Application)
Use this parameter to set the maximum scaling point of the actual value.
See
10.94 (ID 336) Actual Value 1 Minimum Scale
10.98 (ID 340) PID Error Value Inversion
Location in the menu:
P2.2.32
(PID Control Application)
P2.2.1.15
(Pump and Fan Control Application)
AB296635287482en-000301 / DPD00903 | 199
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide