Table 5: Monitoring Values
Index
Monitoring value
Unit
Form
ID
Description
V1.1
Output frequency
Hz
#.##
1
-
V1.2
Frequency reference
Hz
#.##
25
-
V1.3
Motor speed
RPM
#
2
-
V1.4
Motor current
A
Varies
3
-
V1.5
Motor torque
%
#.#
4
-
V1.6
Motor shaft power
%
#.#
5
-
V1.7
Motor voltage
V
#.#
6
-
V1.8
DC-link voltage
V
#
7
-
V1.9
Unit temperature
°C
#
8
-
V1.10
Motor temperature
%
#.#
9
-
V1.11
Analog input 1
V/mA
#.##
13
-
V1.12
Analog input 2
V/mA
#.##
14
-
V1.13
DIN 1, 2, 3
-
-
15
-
V1.14
DIN 4, 5, 6
-
-
16
-
V1.15
DO1, RO1, RO2
-
-
17
-
V1.16
Analog I
out
mA
#.##
26
-
V1.17
Multimonitoring items
-
-
-
-
3.4.2 Basic Parameters (Control Panel: Menu M2 -> G2.1)
Table 6: Basic Parameters G2.1
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.1.1
Min frequency
0.00
P2.1.2
Hz
0.00
101
-
P2.1.2
Max frequency
P2.1.1
320.00
Hz
50.00
102
-
P2.1.3
Acceleration time 1
0.1
3000.0
s
0.0
103
-
P2.1.4
Deceleration time 1
0.1
3000.0
s
0.0
104
-
P2.1.5
Current limit
0.1 x I
H
2 x I
H
A
I
L
107
-
P2.1.6
Nominal voltage of the motor
180
690
V
NX2: 230 V
NX5: 400 V
NX6: 690 V
110
-
P2.1.7
Nominal frequency of the motor
8.00
320.00
Hz
50.00
111
-
P2.1.8
Nominal speed of the motor
24
20 000
RPM
1440
112
-
AB296635287482en-000301 / DPD00903 | 19
Danfoss A/S © 2023.02
Standard Application
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...