9. Install the Terminal Block and AC Bus Bars. Refer to Section 4.11.2 3-Phase Main Voltage Input Terminal
Block Removal and Installation on page 102.
10. Connect the Soft Start AC wires to the AC Bus Bars.
11. Install the Soft Start. Refer to Section 4.14.3 Soft Start Removal and Installation on page 117.
12. Install the top covers. Refer to Section 4.1 Compressor Covers on page 52.
13. Return the compressor to normal operation.
Table 4-28 SCR Diode Values
Positive (+) Lead
Negative (-) Lead
Expected Result
1
2
Infinity or Open
1
3
Infinity or Open
2
1
Infinity or Open
3
1
0.3V and 0.45V
4.18.2.3 Gates Verification
1. Isolate the compressor power as described in Section 1.8 Electrical Isolation on page 22.
2. Using needle-nose pliers, carefully remove the SCR Gate Cable Harness from the SCRs. Refer to Figure
4-140 SCR Connections - TTS300/TGS230 and Figure 4-141 SCR Connections - TTS/TGS/TTH/TGH Rev. F
and Earlier (Except TTS300/TGS230).
3. Using a multimeter set for resistance measurements, place the leads on the two (2) gate terminals. The
value should be between 1 to 25Ω.
4. Reverse the leads. The measured value should be the same.
NOTE
These values can vary depending on the meter being used and the environmental conditions at the time. It is important that the values be
consistent between SCRs.
Table 4-29 SCR Gate Resistance Ranges
SCR Model
Range
All models
1 - 25Ω
4.18.2.4 SCR Temperature Sensor
This section applies to TTS/TGS Revision G and earlier compressors only. The TTS/TGS Revision H and TTH
compressors do not utilize an SCR Temperature Sensor.
Figure 4-145 SCR Temperature Sensor Assembly
4.18.2.5 SCR Temperature Sensor Verification
1. Isolate the compressor power as described Section 1.8 Electrical Isolation on page 22.
2. Remove the Service Side Cover. Refer to Section 4.1.3.1 Service Side Cover Removal and Installation on
Page 144 of 294 - M-SV-001-EN Rev. H 1/23/2023
Summary of Contents for Turbocor TT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK Page 2 of 294 M SV 001 EN Rev H 1 23 2023...
Page 14: ...Page 14 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...Page 16 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...Figure 1 2 New Type Code Page 18 of 294 M SV 001 EN Rev H 1 23 2023...
Page 46: ...Page 46 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 250: ...Page 250 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 268: ...Figure 5 3 Bearing Calibration Flow Page 268 of 294 M SV 001 EN Rev H 1 23 2023...
Page 274: ...Page 274 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 286: ...Page 286 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 290: ...Page 290 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 292: ...Page 292 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...