Installation Guide

Termix Novi

7.0 Troubleshooting

7.1 Troubleshooting in general

In the event of operating disturbances, the following basic features
should be checked before carrying out actual troubleshooting:

the substation is connected to electricity,

the strainer on the DH supply pipe is clean,

the supply temperature of the DH is at the normal level
(summer, at least 60 °C - winter, at least 70 °C),

the differential pressure is equal to or higher than the normal
(local) differential pressure in the DH network – if in doubt, ask
the DH plant supervisor,

pressure on the system - check the HE pressure gauge.

Authorized personnel only

Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.

7.2 Troubleshooting DHW

Problem

Possible cause

Solution

Strainer in supply or return line clogged.

Clean strainer(s).

DHW circulation pump out of order or with
too low setting.

Check circulation pump.

Defective or clogged non-return valve.

Replace – clean.

No electricity.

Check.

Wrong setting of automatic controls, if any.

To adjust an electronic controller for
DHW, pls. note enclosed instructions for
electronic controller.

Scaling of the plate heat exchanger.

Replace – rinse out.

Defective motorized valve.

Check (use manual function) – replace.

Defective temperature sensors.

Check – replace.

Too little or no DHW.

Defective controller.

Check – replace.

DCW is being mixed with the DHW, e.g. in
a defective thermostatic mixing valve.

Check – replace.

Hot water in some taps but not in all.

Defective or clogged non-return valve on
circulation valve.

Replace – clean.

Tap temperature too high; DHW tap load
too high.

Thermostatic valve adjusted to a too high
level.

Check – set.

Scaling of the plate heat exchanger.

Replace – rinse out.

Temperature drop during tapping.

Larger DHW flow than the substation has
been designed for.

Reduce DHW flow.

Thermostatic control valve does not close

Temperature difference between DH
supply and DHW set point too low.

Lower the set point temperature or
increase the DH supply temperature.

Idle temperature too low (for stations
equipped with IHPT).

Set point too low.

Turn thermostat in (+) direction.

12

DEN-GT

VI.GE.N3.02 / LUK38040

Danfoss District Energy

Summary of Contents for Termix Novi

Page 1: ...4 0 Mounting 4 4 1 Mounting 4 5 0 Design 6 5 1 Design 6 5 2 Schematic diagram 7 6 0 Controls 9 6 1 DHW temperature control 9 6 2 Maintenance 11 7 0 Troubleshooting 12 7 1 Troubleshooting in general 1...

Page 2: ...as for small apartment buildings The water heater is available in two sizes either for 1 apartment or up to 4 apartments The Termix Water heater is applicable for decentralized heating systems The hea...

Page 3: ...circumstances interrupt all energy sources to the station if possible and seek expert help In case of discoloured or bad smelling domestic hot water close all shut off valves on the substation inform...

Page 4: ...ry supply Connections 1 Domestic cold water DCW 2 Domestic hot water DHW 3 District heating DH supply 4 District heating DH return Connection sizes DH DCW DHW G ext thread Dimensions mm Type 1 2 with...

Page 5: ...Prior to installation all substation pipes and connections should be cleaned and rinsed Thightening Due to vibration during transport all substation connections must be checked and tightened before i...

Page 6: ...0 Design 5 1 Design Your substation might look different than the substation shown Design description B Heat exchanger DHW N Circulation connection 63 Sieve 74 IHPT controller DHW 6 DEN GT VI GE N3 02...

Page 7: ...Sieve 62 GTU Pressure equalizer 74 IHPT controller DHW HWC DCW DH Supply DH Return Your substation might look different than the schematic diagram shown Schematic description with safety valve B Heat...

Page 8: ...Heating Supply DH Return District Heating Return 5 2 1 Technical parameters Technical parameters Nominal pressure PN 16 Max DH supply temperature 120 C Min DCW static pressure 1 0 bar Brazing materia...

Page 9: ...ning the handle for temperature setting in direction the setting is increased by turning it in direction the setting is decreased Turns DHW Temperature Setting C 0 64 1 61 2 58 3 55 4 52 5 48 6 44 7 4...

Page 10: ...ure equalizer absorbs a possible increase in pressure so a discharge outlet is omitted The GTU Pressure Equalizer may not be applied in systems with hot water circulation 6 1 5 Circulation pipe The ci...

Page 11: ...of all temperatures such as DH supply temperature and DHW temperature Connections Checking all connections for leakages Safety valves The operation of the safety valves should be checked by turning th...

Page 12: ...ctricity Check Wrong setting of automatic controls if any To adjust an electronic controller for DHW pls note enclosed instructions for electronic controller Scaling of the plate heat exchanger Replac...

Page 13: ...isposal Disposal This product should be dismantled and its components sorted if possible in various groups before recycling or disposal Always follow the local disposal regulations Danfoss District En...

Page 14: ...Installation Guide Termix Novi 14 DEN GT VI GE N3 02 LUK38040 Danfoss District Energy...

Page 15: ...0 without electrical equipment covered by this declaration are in conformity with the following directives standards and other normative documents provided that they are used according to our instruct...

Page 16: ...Installation Guide Termix Novi Produced by Danfoss A S 11 2013...

Reviews: